1SFC132104M0201 | Application manual: Waste water pump |
Connection
11
3.2.3
Connecting Start and Stop
terminals to push buttons and PLC
Internal control voltage - Push buttons
The PSTX Softstarter has a built-in holding circuit and
does not require sustained signals on start input. Use
internal control supply voltage from terminals 20 or 21.
Connect start and stop terminals using conventional
circuit with push buttons. See
Figure 6
and
Figure 7.
Connect the white start push button as START and the
black stop push button as STOP in
Figure 7.
Tightening torques and cable dimensions.
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3
L
100-250V
50/60 Hz
K4
K5
K6
Start Stop In0 In1 In2
GND
+24V
N
1SFC132081M0201
External control voltage - PLC
The softstarter can, if required, also be controlled with an
external 24 V DC source from a PLC or similar.
Connect the cables according to
Figure 8
depending on
which type of control method is used.
WARNING
Terminal 13, 14 ,15, 16 and 17 should be
connected using 24V DC only. Other voltages
may damage the softstarter and the warranty may
no longer be valid.
Tightening torques and cable dimensions.
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3
L
100-250V
50/60 Hz
K4
K5
K6
Stop
In0 In1 In2
GND
+24V
N
1SFC132081M0201
Figure 6:
Start and Stop, terminals 13, 14, 18, 19, 20, 21
6
1SFC132081M0201
7
PSTX
L
100-250V
50/60 Hz
K4
K5
K6
Start Stop In0 In1 In2 DGND GND +24V
N
STOP
START
1SFC132081M0201
Figure 7:
Holding circuit (pulse for start is enough)
8
PSTX
L
100-250V
50/60 Hz
K4
K5
K6
Start Stop
In1 In2 DGND
+24V
N
DC
+ -
1SFC132081M0201
In0
GND
STOP
START
Figure 8:
Holding circuit with external control voltage
(pulse for start is enough)
2