Cross section of connection cables
Type of softstarter
PSS18/30-500 ...
PSS44/76-500
PSS50/85-500 ...
PSS72/124-500,
PSS18/30-690 ...
PSS72/124-690
PSS85/147 ...
PSS142/245
PSS175/300 ...
PSS300/515
Main circuit
Connection clamp
Solid/stranded
1 x mm
2
2.5 – 16
6 – 50
See accessories
Solid/stranded
2 x mm
2
2.5 – 16
6 – 25
See accessories
Tightening torque
(recommended)
Nm
2.6
4.5
See accessories
Connection bar
Width and thickness
mm
–
–
Hole diameter
mm
–
–
Tightening torque
(recommended)
Nm
–
–
18
28
Supply and control circuit
Connection clamp
Solid/stranded
1 x mm
2
2.5
2.5
2.5
2.5
Solid/stranded
2 x mm
2
–
–
–
–
Tightening torque
(recommended)
Nm
0.5
0.5
0.5
0.5
E1858D
17.5
ø 8.5
5
E1859D
20
ø 10.2
5
24 Softstarters | 1SFC132005C0201, rev.F
PSS – The flexible range
Technical data
Fuse ratings and power losses
Recommended
ABB Overload protection
Max power loss
at rated I
e
For
Softstarter
Current
range
without
by-pass
2)
with external
by-pass
Max fuse rating - main circuit
1) 3)
Power
requirements
of supply
Bussmann Fuses, DIN43 620 (Knife)
Type
Type
A
W
W
A
Type
size
VA
PSS18/30
TF42DU
7.6 - 18
65
13.5
50
170M1564
000
9
PSS30/52
TF42DU
7.6 - 30
100
14.6
80
170M1566
000
9
PSS37/64
TF42DU
7.6 - 37
120
17.5
125
170M1568
000
9
PSS44/76
TA75DU
18 - 44
142
17.5
160
170M1569
000
9
PSS50/85
TA75DU
18 - 50
160
20.5
160
170M1569
000
10
PSS60/105
TA75DU
18 - 60
190
22
200
170M1570
000
10
PSS72/124
TA75DU
18 - 72
226
30.5
250
170M1571
000
10
PSS85/147
TA110DU
65 - 85
291
56.5
315
170M1572
000
36
PSS105/181
TA110DU
65 - 105
351
61
400
170M3819
1*
36
PSS142/245
TA200DU
66 - 142
462
63
450
170M5809
2
36
PSS175/300
TA200DU
66 - 175
590
117
500
170M5810
2
65
PSS250/430
TA450DU
130 - 250
815
117
700
170M5813
2
65
PSS300/515
TA450DU
130 - 300
965
140
900
170M6813
3
65
1)
For the supply circuit 6 A delayed, for MCB use C characteristics.
2)
Calculated power loss at operational current (Iop) without by-pass.
Ptot = 3 x Iop + VA value
Example: PSS 60/105 running at 52A
Ptot = 3 x 52 + 10 = 166W
3)