- 31 -
Size related data
Recommended
Power
overload relay
Max.
requirements
Type
Current
power loss
Max. fusing rating main circuit
4)
of control
Starting
range
at max. I
e
circuits
Size
capacity
A
W
Bussmann fuses
Ferraz fuses
VA
PS D
75
4,5x
I
e
for 14s
T75 DU
22-80
3)
250A 170M1371
5)
315A 6,6 URD 30 D08 A 0315
40
110
4,5x
I
e
for 14s
T135 DU
65-135
3)
315A 170M2619
5)
400A 6,6 URD 30 D08 A 0400
40
145
4,5x
I
e
for 14s
T200 DU
100-150
3)
400A 170M2621
5)
500A 6,6 URD 30 D08 A 0500
40
175
4,5x
I
e
for 14s
T200 DU
100-200
2)
450A 170M3020
6)
500A 6,6 URD 30 D08 A 0500
65
210
5x
I
e
for 7s
T450 DU
130-235
2)
500A 170M3021
6)
530A 6,6 URD 30 D08 A 0550
65
250
5x
I
e
for 7s
T450 DU
130-310
2)
630A 170M4016
6)
550A 6,6 URD 31 D08 A 0550
65
300
5x
I
e
for 7s
T450 DU
165-310
2)
700A 170M4017
6)
630A 6,6 URD 31 D08 A 0630
65
370
5x
I
e
for 7s
T900 DU
265-500
2)
900A 170M5015
6)
900A 6,6 URD 32 D11 A 0900
90
470
5x
I
e
for 7s
T900 DU
265-500
2)
1250A 170M5018
6)
1250A 6,6 URD 33 D11 A 1250
90
570
5x
I
e
for 7s
T900 DU
265-650
2)
1500A 170M6018
6)
1250A 6,6 URD 33 D11 A 1250
90
720
5x
I
e
for 7s
T900 DU
355-850
2)
1800A 170M6020
6)
2000A 6,6 URD 33 TTF 2000
90
840
5x
I
e
for 7s
T900 DU
465-850
2)
1800A 170M6020
6)
2000A 6,6 URD 33 TTF 2000
90
PS DH
30
5x
I
e
for 25s
1)
3)
125A 170M1368
5)
160A 6,6 URD 30 D08 A 0160
40
45
5x
I
e
for 25s
1)
3)
200A 170M2617
5)
200A 6,6 URD 30 D08 A 0200
40
60
5x
I
e
for 25s
1)
3)
250A 170M1371
5)
250A 6,6 URD 30 D08 A 0250
40
75
5x
I
e
for 25s
1)
3)
315A 170M2619
5)
315A 6,6 URD 30 D08 A 0315
40
110
5x
I
e
for 25s
1)
3)
400A 170M2621
5)
450A 6,6 URD 30 D08 A 0450
40
145
5x
I
e
for 25s
1)
3)
450A 170M3020
6)
500A 6,6 URD 30 D08 A 0500
65
175
5x
I
e
for 25s
1)
3)
500A 170M3021
6)
550A 6,6 URD 30 D08 A 0550
65
210
5x
I
e
for 25s
1)
2)
630A 170M4016
6)
630A 6,6 URD 31 D08 A 0630
90
250
5x
I
e
for 25s
1)
2)
700A 170M4017
6)
700A 6,6 URD 32 D08 A 0700
90
300
5x
I
e
for 25s
1)
2)
900A 170M5015
6)
900A 6,6 URD 32 D08 A 0900
90
370
5x
I
e
for 25s
1)
2)
1000A 170M5016
6)
1000A 6,6 URD 33 D08 A 1000
90
470
5x
I
e
for 25s
1)
2)
1250A 170M5018
6)
1250A 6,6 URD 33 D08 A 1250
90
570
5x
I
e
for 25s
1)
2)
1500A 170M6018
6)
250A 6,6 URD 33 TTF A 1600
90
720
5x
I
e
for 25s
1)
2)
1800A 170M6020
6)
250A 6,6 URD 233 PLAF 2000
90
1) Electronic overload relay built in
2) Total power loss: P
Ltot
= (3 x I
e
x 1,0) + 100 (W)
3) Total power loss: P
Ltot
= (3 x I
e
x 1,0) + 50 (W)
4) For the control circuit: 6 A delayed
5) Fuse holder 170H 1007
6) Fuse holder 170H 3004