12 EtherNet/IP interface details
This section lists all the available classes, attributes and
services included in the EtherNet/IP Interface.
The flow meter supports the following standard objects:
• Identity Object (0x01)
• Message Router Object (0x02)
• Assembly Object (0x04)
• Connection Manager Object (0x06)
• Device Level Ring Object (0x47)
• File (0x37)
• Quality of Service Object (0x48)
• TCP/IP Interface Object (0xF5)
• Ethernet Link Object (0xF6).
Abbreviations for service names:
• GAA = Get Attribute All
• GAS = Get Attribute Single
• SAA = Set Attribute All
• SAS = Set Attribute Single.
[Identity] 0x01
This object provides identification data from and general
information about the device.
Service Code
Service Name
0x0E
GAS
0x01
GAA
Table 12 Class-Services
Attr ID
Name
Access Rule
Data Type
Value
1
Revision
Get
UINT
1
2
Max
Instance
Get
UINT
1
3
Number of
Instances
Get
UINT
1
6
Maximum ID
Number
Class
Attributes
Get
UINT
7
7
Maximum ID
Number
Instance
Attributes
Get
UINT
7
Table 13 Class attributes
Reset-Type
Description
0
Emulated power cycle reset (Power supply off/on, warm
start)
1
The device is reset to factory settings and restarted.
Communication parameters are also reset to factory
settings, for example, IP address
2
Return to factory settings except communications
parameters
Table 14 Reset
Service Code
Service Name
0x0E
GAS
Table 15 Instance-Services
Attr ID
Name
Access Rule
Data Type
1
Vendor ID
Get
UINT
2
Device Type
Get
UINT
3
Product Code
Get
UINT
4
Revision
Get
STRUCT of
0
Major Revision
Get
USINT
0
Minor Revision
USINT
5
Status
Get
WORD
6
Serial Number
Get
UDINT
7
Product Name
Get
SHORT_ STRING
Table 16 Instance attributes
Bit(s)
Description
0-3
Not supported (= 0)
4-7
Extended Device Status (Refer to
)
8
Easily recoverable error
The device detected an internal error that can probably be
corrected. The error does not put the device in Error State.
9
Minor unrecoverable error
The device detected an internal error that probably cannot
be corrected. Error does not put the device in Error State.
10
Serious recoverable error
The device detected an internal error that triggered the
error status
Serious recoverable error
in the sensor.
11
Serious unrecoverable error
The device detected an internal error that triggered the
error status
Serious unrecoverable error
in the sensor.
12-15
Reserved
Table 17 Description of Bits related for Attribute 5
ID
Description
0
Self-test or unknown (not supported)
1
Firmware update in progress (not supported)
2
At least one I/O connection is faulty (not supported)
3
No I/O connection established
4
Non-volatile storage is insufficient (not supported)
5
Serious error (Bit 10 - 11)
6
At least one I/O connection in
run mode
(not supported)
7
At least one I/O connection established, all in
idle mode
8
0
9
Reserved
10-15
0 (not supported)
Table 18 Description of Bits 4 to 7 for Attribute 5