Grounding the operator panel
Section 7 Additional Installation Tips
2.
Connect a wire or grounding braid, that is sized correctly according to local
electrical codes, between the chassis of the operator panel and the closest
grounding point on the door, see 3 in drawing above.
3.
Connect a strong but short grounding braid between the door and the device
cabinet, see 4 in drawing above.
4.
Twist the cables onto the 24 V DC feed, see 5 in drawing above.
2 turns around the ferrite core provide 4 times the suppression of 1 turn.
3 turns around the ferrite core provide 9 times the suppression of 1 turn.
A ferrite core suppresses disturbances to the 24 V feed, see 6 in drawing above.
The grounding wires should be short and the conductor should have a large area.
A long, thin grounding wire has a very high impedance (resistance) at high
frequencies and does not guide disturbances to the ground.
Multi-wire conductors are better than single wire conductors with the same area.
A braided conductor wire with the same area is even better. The best is a short,
thick grounding braid.
34
3BSE069463-600 Rev D
Содержание PP885M
Страница 1: ...Compact Product Suite Panel 800 Version 6 PP885 Hardware and Installation ...
Страница 2: ......
Страница 3: ...Panel 800 Version 6 PP885 Hardware and Installation ...
Страница 6: ...6 3BSE069463 600 Rev D ...
Страница 16: ...Appearance of Air in Touch Screen Section 2 Safety Precautions 16 3BSE069463 600 Rev D ...
Страница 24: ...Section 4 Technical Data 24 3BSE069463 600 Rev D ...
Страница 32: ...PP885 Outline Section 6 Operator Panel Drawings 32 3BSE069463 600 Rev D ...