Dual Input Feed Connections
In the dual input feed configuration, two separate AC inputs are connected to the UPS (one for the inverter
and one for the bypass).
Figure 18: UPS Diagram with Dual Input Feed
When the Earth system of the inputs are different, a transformer should be connected to the inputs. Figure 19,
Figure 20, and Figure 21 show the possible ways of connecting the inputs to the transformers.
Figure 19: UPS with transformer in the normal AC input
Figure 20: UPS with transformer in the bypass input
Figure 21: UPS with transformer in normal and bypass inputs
Follow the steps below for cabling the UPS:
1. IMPORTANT: Connect the Earth wire
2. Ensure that the jumper JP is disconnected
3. Connect the input, output and bypass cables
Use appropriate tools and terminal splices to guarantee a reliable contact between the wires and the terminal
blocks.
Figure 22: Dual Input Feed connections for 6kVA units