Appendix A
CS121 SNMP card available parameters (valid for CS121 Basic, CS121 ModBus, CS121 Advanced)
The parameters available from CS121 SNMP cards are herein described
Parameter
Units
Type
Available interface
Modbus register
Measurement Parameters
Input Voltage per Phase
V
Input
Webserver / Modbus
104, 105, 106
Input Frequency
Hz
Input
Webserver / Modbus
111, 112, 113
Output Voltage per Phase
V
Output
Webserver / Modbus
97, 98, 99
Output Current per Phase
A
Output
Webserver / Modbus
143, 144, 145
Output Load in Percentages
%
Output
Webserver / Modbus
100, 101, 102
Output Frequency
Hz
Output
Modbus
168
Total Output Power
kW
Output
Webserver / Modbus
160, 161, 162
Battery Voltage
V
Battery
Webserver / Modbus
110
Estimated Runtime
min
Battery
Webserver / Modbus
108
Temperature
°C
Environmental
Webserver / Modbus
107
UPS Status Information
On shutdown
Webserver / Modbus
109
On inverter
Webserver / Modbus
109
On battery
Webserver / Modbus
109
UPS Alarms
Battery Low
Webserver / Modbus
117
Input Bad
Webserver / Modbus
120
On Bypass
Webserver / Modbus
123
General Fault
Webserver / Modbus
132
Test In Progress
Webserver / Modbus
138
Shutdown imminent
Webserver / Modbus
137
Diagnose test failed
Webserver / Modbus
133