Section-10
04-3004_S10_TDS_ABB_POWERSCALE_10-50 kVA_EN_150113.doc
Page 10/20 ABB
Printed in Switzerland
– Modifications reserved
RS232 on Sub-D9 port
For monitoring and integration in network management
Customer Interfaces :
Inputs DRY PORT
1 Remote Shut down [EMERGENCY OFF (Normally closed)]
1 GEN-ON (Normally open)
1
Programmable Customer’s Inputs (Normally open)
1 Temp. Sensor for Battery Control
1 12 vdc source (max. 250 mA)
RJ45 port
For multidrop purpose
Power Management Display (PMD)
LCD display
OPTIONAL ITEMS
Relay card + USB Including:
Customer Interfaces:
5 output DRY PORTS
RS232 on USB port
Common alarm
Load on bypass
Battery low
Load on inverter
Mains failure
For remote signalling and automatic computer shutdown
SNMP Card (
slot already included
)
SNMP card
For monitoring and integration in network management
10.8.1 POWER MANAGEMENT DISPLAY (PMD)
The user-friendly PMD consists of three parts the MIMIC DIAGRAM, CONTROL KEYS and LCD that provides the
necessary monitoring information about the UPS.
10.8.2 MIMIC DIAGRAM
The mimic diagram serves to give the general status of the UPS. The LED-indicators show the power flow status
and in the event of mains failure or load transfer from inverter to bypass and vice-versa the corresponding LED-
indicators will cha
nge colour from green (normal) to red (warning). The LED’s LINE 1 (rectifier) and LINE 2
(bypass) indicate the availability of the mains power supply. The LED’s INVERTER and BYPASS if green indicate
which of the two are supplying power to the critical load. The LED-indicator BATTERY is normally lit green, and
when it supplies the load is blinking. The LED-indicator ALARM is a visual indication of any internal or external
alarm condition. At the same time the audible alarm will be activated.
10.8.3 DISPLAY
The 2 x 20 character LCD simplifies the communication with the UPS. The menu driven LCD enables the access to
the EVENT REGISTER, or to monitor the input and output U, I, f, P, Autonomy Time and other Measurement’s, to
perform commands like start-up and shut-down of UPS or load transfer from UPS to BYPASS and vice-versa and
finally it serves for the DIAGNOSIS (SERVICE MODE) for adjustments and testing.