PositionMaster EDP300
DIGITAL POSITIONER | OI/EDP300-EN REV. D
51
Menu / parameter
Value range
Description
Easy Setup (continued)
Autoadjust Mode
Full, Controller, Valve Range,
Zero, Locked
Use this parameter to define the mode or scope of the Auto Adjust function.
• Full: Complete automatic adjustment
• Controller: Determine control parameters only
• Zero: Determine the 0 % position only
• Valve Range: Determine stops only
• Locked: Automatic adjustment blocked
Note
On valves where slip-stick effect is significant, valve vibration can be reduced by increasing the value of
the ‘Zone’ parameter.
Start Autoadjust
Start
The following values are determined during Auto Adjust:
• Direction of action of the actuator
• Direction of action of the reset spring
• Actuator travel of the actuator / final control element
• Stroke time for both directions
• Control parameters
• Offset for the I/P module
• Static friction of the actuator / final control element
• Dynamic friction of the actuator / final control element
Содержание PositionMaster EDP300
Страница 82: ...82 PositionMaster EDP300 DIGITAL POSITIONER OI EDP300 EN REV D 17 Appendix Control Drawing 901305 ...
Страница 83: ...PositionMaster EDP300 DIGITAL POSITIONER OI EDP300 EN REV D 83 ...
Страница 84: ...84 PositionMaster EDP300 DIGITAL POSITIONER OI EDP300 EN REV D 17 Appendix Control Drawing 901305 ...
Страница 85: ...PositionMaster EDP300 DIGITAL POSITIONER OI EDP300 EN REV D 85 ...
Страница 86: ...86 PositionMaster EDP300 DIGITAL POSITIONER OI EDP300 EN REV D 17 Appendix Control Drawing 901305 ...
Страница 87: ...PositionMaster EDP300 DIGITAL POSITIONER OI EDP300 EN REV D 87 ...