PositionMaster EDP300
| OI/EDP300-EN 39
8.4.5
Menu: Input / Output
…/ Input / Output
Mask contents
Value range
Description
DIGITAL INPUT
DI Function
DI Default SP
DI Logic
Selection of functions or states that are executed or adopted if the "digital input" has been
activated.
ALARM OUTPUT
ALARM LOGIC
DO ALARM MASK
Alarm Simulation
Use this parameter to configure the alarm output via which a general alarm can be issued.
Depending on the activated Namur classification group, it is also possible for the general alarm to
be issued as an alarm current.
ANALOG FEEDBACK
Analog Out Min.
Analog Out Max.
Feedb. Charact.
AO ALARM MASK
AO Simulation
The current valve position (or the "back-calculated valve flow characteristic", if this option is being
used) is fed back as a current signal via analog position feedback.
Depending on the activated Namur classification group, it is also possible for the general alarm to
be issued as an alarm current.
DIGIT. FEEDBACK
SWITCH 1
SW 1 MASK MAP
SWITCH 2
SW 2 MASK MAP
Digital feedback can be used to configure two limit switches which are able to report when a
value is reached or exceeded, via a current signal. Additionally, diagnostics bits can be output via
the second switch.
UNIVERSAL INPUT
UI SP Value Max.
UI SP Value Min.
UI Damping
UI Charact.
UI Out Value Min.
UI Out Value Max.
Use this menu item to configure and simulate the universal input.
Menu: DIGITAL INPUT
... / …/ DIGITAL INPUT
Mask contents
Value range
Description
DI Function
Off
Hold Last SP
Hold User SP
Hold Last Pos.
Press. Out1
Vent. Out2
Freeze Outputs
Partial Stroke Test
Service Required
Safety Position
Local Conf Lock
Local Operation Lock
Lock all
Off – No function
Hold Last SP – Last setpoint is retained
Hold User SP – Substitute value for setpoint (defined in "DI Default Setp.")
Hold Last Pos. – Hold last position
Press. Out1 – Vent output 1
Vent. Out2 – Vent output 2
Freeze Outputs – Close pneumatic outputs
Partial Stroke Test – Start partial stroke test
Service Required – Output diagnostics bit via digital feedback
Safety Position – Approach safety position
Local Conf Lock – Lock local configuration
Local Operation Lock – Lock local operation
Lock all – Lock all operation and setting options.
DI Default SP
0 … 100%
The position defined using this parameter is approached when the "digital input" function has
been set to "Hold User SP" and the digital input has been activated.
Use this parameter to configure the contact logic for activating the digital input.
IMPORTANT (NOTE)
For the following parameters, the contact logic is always "active low" or "off":
—
Safety Position
—
Local Conf Lock
—
Local Operation Lock
—
Lock all
DI Logic
Active High
Active Low