Parameter address (Offset)
Data type
Function
Value range and coding
005BH
Byte
Synchronisation day
00H = ignore
01H = 1st day
...
1FH = 31st day
005CH
Byte
Message line
00H = none
01H = Text line 1
...
0AH = Text line 10
005DH
Float
Value input for threshold
1....7,500E6
3F 80 00 00...4A E4 E1 C0H (float format)
0061H
Byte
Relay output for accounting
threshold
00H = off
01H = DO 1
...
14H = DO 20
0062H
Byte
Print format for accounting
table
01H = Channel line
02H = Interval time
04H = Min. value
08H = Max. value
10H = Mean value
20H = Sum
0063H
Byte
Print sum if threshold
exceeded
00H = no
01H = yes
0064H
Byte
Register the sum instead of
measured value
00H = no
01H = yes
0067H
CHAR
Free unit of measurement
(max. 7 characters)
00H = 1st character
01H = 2nd character
...
06H = 7th character
006EH
CHAR
Scale text line (max. 32
characters)
00H = 1st character
01H = 2nd character
...
1FH = 32nd character
00A4H
Byte
Format of the scale line
00H = no printout
01H = 2 graduations
02H = 3 graduations
03H = 5 graduations
04H = free input
00A5H
Byte
Enable user linearisation
00H = off
01H = on
00A6H
Word
Tie point x1
0000...03E8H = 0...1000
00A8H
Word
Tie point y1
0000...03E8H = 0...1000
00AAH
Word
Tie point x2
0000...03E8H = 0...1000
00ACH
Word
Tie point y2
0000...03E8H = 0...1000
...
...
...
...
00DEH
Word
Tie point x15
0000...03E8H = 0...1000
00E0H
Word
Tie point y15
0000...03E8H = 0...1000
00E2H
Word
Tie point x16
0000...03E8H = 0...1000
00E4H
Word
Tie point y16
0000...03E8H = 0...1000
16
Parameters