background image

The OVRHSP(SR) series unit is a Type 1 SPD which is 
suitable for use in both Type 1 and Type 2 SPD applications. 
The OVRHSP(SR) series unit is a one-port SPD and is to be 
connected in parallel with the electrical system. It may be 
connected via a circuit breaker, molded case switch, fused 
switch, or connected directly to the bus of the panelboard or 
switchboard it is protecting. If direct bus connection is used, 
ABB recommends installing the OVRHSP(SR) series unit behind 
a disconnect switch or other disconnecting means for ease of 
serviceability.

If the SPD is connected to a dedicated OCPD, a 60A breaker is 
recommended (30A minimum, 200A maximum).

Upstream overcurrent protection device

Table 2: Maximum recommended conductor size

OVRHSP models 

Conductor size

OVRHSP120

#6 AWG

OVRHSP160

#6 AWG

OVRHSP200

#4 AWG

OVRHSP240

#4 AWG

OVRHSP300

#4 AWG

OVRHSP400 

#4 AWG

–  60 through 100kA units and all OVRHSR units are furnished 

with #10 AWG leads. Leads should be shortened during 
installation in order to minimize conductor length.

–  120 through 400kA units are shipped with compression box 

lugs. The set screws on the box lugs should be torqued to  
2.3 Nm (20 in-lbs.).

–  Terminals are identified with markers (Phase A, B, C, Line 1, 

Line 2, Neutral or Ground)

Conductor sizing and routing (OVRHSP)

ABB recommends installing the OVRHSP unit by following 
conductor size for phase, ground and neutral connections. The 
conductor length should be as short as possible to ensure the 
maximum level of protection.

 

CAUTION: 

The OVRHSP(SR) series unit’s performance will be limited 
severely if the conductors are (a) too long, (b) are of too 
small a wire gauge, (c) have too many bends or (d) have 
sharp bends. For optimum performance never exceed 
3.048 meters (10 ft.) conductor lengths.

The factors listed above should be addressed during the 
design of an installation to reserve a suitable place for the 
OVRHSP(SR) series unit next to its point of connection to the 
electrical system. The selected mounting location should allow 
for the shortest possible conductor runs and a direct route 
with a minimum of bends. If bends are required, they should be 
sweeping bends. Do not make sharp 90° bends for appearance 
purposes because they will severely decrease the effectiveness 
of OVRHSP(SR) series unit.

Binding or twisting conductors together using tie-wraps or 
electrical tape increases the protection performance of the 
device.

The conductor length should be as short as possible to ensure 
the maximum level of protection. Wires are marked with  
(Phase A, B, C, Line 1, Line 2, Neutral or Ground) depending  
on the model.

6 Product manual | 

OVRHSP/OVRHSR surge protective device

Conductor sizing and routing

Содержание OVRHSP Series

Страница 1: ...d for any orientation and indoor outdoor applications 5 year standard warranty OVRHSP OVRHSR Surge protective devices Installation operation and maintenance manual Product manual OVRHSR product features UL Listed 1449 4th Edition for Type 1 and Type 2 SPD applications Compact design to allow the SPD to be recessed into the wall Fail safe design with individually fused Metal Oxide Varistors MOVs el...

Страница 2: ...ting 6 Upstream overcurrent protection device 6 Mounting 7 Indoor vs Outdoor installation 7 Conduit openings 8 Electrical connections 9 Connecting Form C dry contacts 9 Remote monitoring 10 Verification and power up 11 Troubleshooting 12 Standards and listings 12 Warranty period 12 2 Product manual OVRHSP OVRHSR surge protective device ...

Страница 3: ...the OVRHSP SR series unit is connected without disconnecting the OVRHSP SR series units conductors including phases neutral and ground Warning lnstallation by person with electrotechnical expertise only Warnung lnstallation nur durch elektrotechnische Fachkraft Avertissement lnstallation uniquement par des personned qualifiées électrotechnique iAdvertencia La instalación deberá ser realizada única...

Страница 4: ...Add suffix N Transient filter surge counter and stainless steel enclosure Add suffix T 1 These are the only voltages available on the 60 80 and 100kA systems NOTES xxx denotes surge rating per phase 60 80 100 120 160 200 240 300 400 OVRHSR units are only available in 120 and 160kA The power system operation frequency is between 47 63Hz OVRHSP SR 100 120 1P 1 Model kA rating Voltage Configuration O...

Страница 5: ... WITH OVRHSP SR L1 N L2 N G L1 L2 N G Figure 3 3 phase Wye 4 wire 30 200 AMP 3 POLE 1 CIRCUIT BREAKER OVRHSP SR EARTH GROUND Xo BOND B N C A N G N G CONDUCTORS 2 FURNISHED WITH OVRHSP SR A B C G N A B C 30 200 AMP 3 POLE 1 CIRCUIT BREAKER B C A N G OVRHSP SR CONDUCTORS 2 FURNISHED WITH OVRHSP SR A B C G A B C G EARTH GROUND OVRHSP OVRHSR surge protective device Product manual 5 1 All OVRHSP SR ser...

Страница 6: ...al or Ground Conductor sizing and routing OVRHSP ABB recommends installing the OVRHSP unit by following conductor size for phase ground and neutral connections The conductor length should be as short as possible to ensure the maximum level of protection CAUTION The OVRHSP SR series unit s performance will be limited severely if the conductors are a too long b are of too small a wire gauge c have t...

Страница 7: ...ywall is not a structural material If back wall is not made of structural material the electrician can create brackets to hold the SPD to the adjacent studs After the drywall has been installed install Flush Mounting Plate FMP by first removing the OVRHSR enclosure lid Place the FMP over enclosed body Attach the FMP to the wall using the enclosed hardware kit Screw the lid back on to the enclosure...

Страница 8: ...nings OVRHSP Figure 6A Conduit Openings and Enclosure Mounting Dimensions OVRHSP Dim OVRHSP 60 80 100 OVRHSP 120 160 OVRHSP 200 240 300 400 H1 152 4 6 00 254 0 10 00 355 6 14 00 H2 171 5 6 75 273 1 10 75 374 7 14 75 H3 190 5 7 50 292 1 11 50 393 7 15 50 W1 152 4 6 00 203 2 8 00 304 8 12 00 W2 101 6 4 00 152 4 6 00 254 0 10 00 D 157 5 6 20 157 5 6 20 D1 105 7 4 16 D2 50 8 2 00 Weight 4 5 kg 10 lbs ...

Страница 9: ...C The Form C contacts come pre wired with 254 mm 36 in of 20 AWG conductors on the OVRHSP 60 to 100kA models and on all OVRHSR models When input power is present on all phases terminals NO Normally Open and COM Common are an open circuit and terminals NC Normally Closed and COM are a closed circuit The contacts change state when the unit has encountered failure to one or more phases The installer ...

Страница 10: ...to ensure proper installation Figure 7 Wire connections Contacts shown in de energized state alarm condition Figure 8 Terminal block Contacts shown in energized normal state no fault condition Models OVRHSP 120kA 400kA For these models the Form C contacts must be wired by the installer See Figure 8 for the Form C contact configuration and terminal location on the monitor board The annotations on t...

Страница 11: ...tion 60 100kA and OVRHSR units Verify that all indicating lights are illuminated The lights extinguish only upon failure of one or more phases indicating an alarm condition Audible alarm should not operate under normal conditions The audible alarm can be muted by pressing the Alarm silence button which subsequently will illuminate the Alarm silenced light Pressing the Alarm silence button again wi...

Страница 12: ...d using a voltage tester The following standards and listings apply to the OVRHSP SR series product line UL Listed 1449 4th Edition for Type 1 and Type 2 SPD applications cUL and UL 1283 Meets Requirements for UL 96A Compliant to IEEE C62 41 1 2002 C62 41 2 2002 and C62 45 2002 NFPA 70 NEC Article 285 RoHS Compliant Troubleshooting Standards and listings Warranty Period OVRHSP SR series AC All 5 y...

Отзывы: