![ABB OVRHSP 1201 P Series Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/abb/ovrhsp-1201-p-series/ovrhsp-1201-p-series_installation-operation-and-maintenance-manual_4764004.webp)
Confirm that the voltage(s) and service configuration shown on the OVRHSP(SR) series product label are consistent
with the voltage and service configuration of the facility. A model number is on the right side of the OVRHSP(SR)
series unit. Each model number corresponds to the configurations printed in Table 1:
Pre-installation checklist
Confirm that the environmental conditions are consistent with the following ranges:
– Ambient temperatures: Between -40º to 70ºC (-40° to +158°F).
– Relative humidity: Between 5% and 95% non-condensing.
– Altitude: Less than 4000 m (13,000 feet).
Table 1: Configuration table
OVRHSP series options
Advanced monitoring (available in 60–100kA units only)
Add suffix 1 (Includes dry relay contacts, audible alarm,
alarm silence button, fault light)
Surge counter (Not available on OVRHSP 60–100kA units or the OVRHSR series)
Add suffix 2
Transient filter (Meets UL 1283) (Not recommended when using telecommunication rectifiers)
Add suffix 3
Stainless steel enclosure
Add suffix 4
Transient filter and advanced monitoring
Add suffix A
Transient filter and surge counter
Add suffix B
Transient filter and stainless steel enclosure
Add suffix C
Surge counter and stainless steel enclosure
Add suffix D
Stainless steel enclosure and advanced monitoring
Add suffix M
Stainless steel enclosure, transient filter and advanced monitoring
Add suffix N
Transient filter, surge counter and stainless steel enclosure
Add suffix T
1
These are the only voltages available on the 60, 80, and 100kA systems.
NOTES:
– xxx denotes surge rating per phase (60, 80, 100, 120, 160, 200, 240, 300, 400)
– OVRHSR units are only available in 120 and 160kA.
– The power system operation frequency is between 47–63Hz.
OVRHSP(SR) 100 120 1P 1
Model
kA rating
Voltage
Configuration
Options
Sample model number scheme
4 Product manual |
OVRHSP/OVRHSR surge protective device
✓
Example of a SPD model number: OVRHSP(SR)1001201P1
Model
Voltage
L-N voltage range
L-L voltage
Configuration
OVRHSP(SR)xxx1201P
1
120V
108-132V
N/A
1-phase, 2-wire + ground
OVRHSP(SR)xxx2401P
1
240V
216-264V
N/A
1-phase, 2-wire + ground
OVRHSP(SR)xxx1202P
1
120/240V
108-132V
216-264V
2-phase, 3-wire + ground
OVRHSP(SR)xxx1203Y
1
120/208V
108-132V
187-229V
3-phase Wye, 4-wire + ground
OVRHSP(SR)xxx2203Y
1
220/380V
198-242V
342-418V
3-phase Wye, 4-wire + ground
OVRHSP(SR)xxx2403Y
1
240/415V
216-264V
374-457V
3-phase Wye, 4-wire + ground
OVRHSP(SR)xxx2773Y
1
277/480V
249-305V
432-528V
3-phase Wye, 4-wire + ground
OVRHSP(SR)xxx6003Y
347/600V
312-382V
540-660V
3-phase Wye, 4-wire + ground
OVRHSP(SR)xxx2403H
1
120/240V
108-132V (Phases A and C)
187-229V (Phase B)
216-264V
3-phase High-Leg Delta, 4-wire + ground
OVRHSP(SR)xxx2403D
1
240V
N/A
216-264V
3-phase Delta, 3-wire + ground
OVRHSP(SR)xxx3803D
380V
N/A
342-418V
3-phase Delta, 3-wire + ground
OVRHSP(SR)xxx4803D
480V
N/A
432-528V
3-phase Delta, 3-wire + ground
OVRHSP(SR)xxx6003D
600V
N/A
540-660V
3-phase Delta, 3-wire + ground