5. Connecting
Only an authorised electrician may perform the electrical installation and
maintenance of motorized change-over switches. Do not attempt any installation
or maintenance actions when a motorized change-over switch is connected to the
electrical mains. Before starting work, make sure that the change-over switch is de-
energised.
5.1 Control circuit
The control voltage (output C = 24Vdc) on the control terminal is non-isolated, see
box 2 in Figure 5.1
When relay outputs are used with inductive loads (such as relays, contactors and
motors), they must be protected from voltage spikes using varistors, RC-protectors
(AC current) or DC current diodes (DC current).
Do not couple power for the control terminal. See the correct terminal for the
power supply in Figure 5.1