3.5.5 Connecting incoming mains and protective earth to the controller
Note
How to manufacture a cable with connector is described in section
connector for incoming mains on page 75
DANGER
A residual current device (RCD) must be installed. See
Note
The controller must be installed towards a 3-phase grounded Wye electrical
configurations. The use of three phase power with delta connection voids
warranty.
Note
For UL installations, the integral solid state short circuit protection does not
provide branch circuit protection. Branch circuit protection must be provided in
accordance with the Manufacturer Instructions, National Electrical Code and any
additional local codes.
Introduction
Before incoming mains is connected to the controller, the following prerequisites
must be fulfilled:
•
An external circuit breaker or fuse must be installed. See
.
•
The cabinet must be connected to protective earth. See
.
•
A residual current device (RCD) must be installed. See
.
Location of incoming mains connection
xx2100001260
Continues on next page
Product manual - OmniCore V250XT
77
3HAC073447-001 Revision: B
© Copyright 2020-2022 ABB. All rights reserved.
3 Installation and commissioning
3.5.5 Connecting incoming mains and protective earth to the controller
Содержание OmniCore V250XT
Страница 1: ...ROBOTICS Product manual OmniCore V250XT ...
Страница 2: ...Trace back information Workspace 22A version a10 Checked in 2022 03 02 Skribenta version 5 4 005 ...
Страница 34: ...This page is intentionally left blank ...
Страница 50: ...This page is intentionally left blank ...
Страница 174: ...This page is intentionally left blank ...
Страница 410: ...This page is intentionally left blank ...
Страница 418: ...This page is intentionally left blank ...
Страница 454: ......
Страница 455: ......