Technical data
Voltage and current limits
Rated AC voltage
220 … 240 V +/-20%, 50/60 Hz +/-10%
Output current
Max 4 A
Operating time
2 s
Main circuit connections
X11:1
Line I Phase
X11:2
Line I Neutral
X13:1
Line II Phase
X13:2
Line II Neutral
X12:1
Motor operator Phase
X12:2
Motor operator Neutral
Connection cables
Supply side cables of the main circuit
0,2 ... 2,5 mm
2
Load side cables of the main circuit
0,2 ... 2,5 mm
2
External transformer
When ODPS230 is used in network where N is not connected an external transformer must be used to drop voltage
level. Transformer has to be Main to Phase transformer and isolative. Effective value depends on the size of the mo-
tor operator. See Connection diagram.
Dielectric properties
Overvoltage category
III
IEC 60947- 1 Rated impulse withstand voltage (Uimp), basic
insulation
4,0 kV
IEC 60947-1 Dielectric test
1,89 kV, 50 Hz, 5 s
IEC 60092-504 Insulation resistance measurement
> 100 M
Ω
, 500 V DC
Mechanical characteristics
Material of Enclosure
Self-extinguishing thermoplastic, UL 94 V-0
Degree of protection
IP 20
Dimensions
Height
90 mm
Width
32 mm
Depth
130 mm
Environmental conditions
Ambient air temperature
-25 … +60 °C
Altitude of the site of installation
< 2000 m
IEC 60068-2-30 Humidity, relative
< 93 %, T = -25 ... +60 °C
IEC 60947-1 Pollution degree
3
Mechanical tests
IEC 60068-2-6 Vibration test
5 Hz to 13,2 Hz: +/-1 mm
13,2 Hz to 100 Hz: +/- 0,7 g
Q does not exceed 5
Duration 90 min at 30 Hz or at each resonance fre-
quency
IEC 60068-2-27 Shock test
Acceleration 100 m/s
2
peak (10g
n
) and 150 m/s
2
peak
(15g
n
). Pulse duration: 11 ms
Transport and storage
Ambient air temperature
-40 … +70 °C
EMC characteristics
IEC 61000-4-2 Electrostatic discharge immunity test
8kV (Level 3) Air discharge
4kV (Level 2) Contact discharge
IEC 61000-4-3 Radiated, radio-frequency, electromagnetic
field immunity test
Level 3
IEC 61000-4-4 Electrical fast transient/burst immunity test
Level 3
IEC 61000-4-5 Surge immunity test
2kV Phase to Neutral
IEC 61000-4-6 Immunity to conducted disturbances, induced
by radio-frequency fields
Level 3
IEC 61000-4-8 Power frequency magnetic field immuntiy test Level 4
CISPR 11 Electromagnetic disturbance characteristics
(Emission)
Group 1 Class B
Table 2 Technical data