RaMa 19P - 4PG - 7RG
Digital In-
Digital In+
Status-
Console
Section 2 Interface specifications
Figure 4. Connection to Console Port
The console port shown in the
Figure 4
can be used to connect to the CLI
(Command Line Interface). The console connector is a micro USB cable that
connects to a FTDI FT232R USB to serial converter internally. For drivers
please see www.ftdichip.com and download the appropriate VCP driver.
12
3BSE080639
* External supply current capability for proper start-up
Power
Rated Voltage
115 to 230 VAC
Operating voltage
90 to 264 VAC
Maximum nominal current consumption
350mA @ 115 VAC 60Hz
210mA @ 230 VAC 50 Hz
Inrush current
75mA2 @ 115 VAC
340mA2 @ 230 VAC
Rated frequency
50/60 Hz
Startup current*
2x nominal current
Polarity
Not applicable
Redundant power input
No
Isolation to
All other
Connection
Detachable screw terminal
Connector size
0.2 – 2.5 mm
2
(AWG 24 – 12)
Shielded cable