Section 3 Interface Modules
Type Tests and Environmental Conditions
3BSE080635
39
Environmental
phenomena
Test
Description
Test levels
ESD
EN 61000-4-2
Enclosure contact
±6 kV
Enclosure air
±8 kV
RF field AM
modulated
IEC 61000-4-3
Enclosure
20 V/m 80% AM (1 kHz), 80 –
2700 MHz
Fast transients
EN 61000-4-4
Power port
±2 kV
Signal ports
±2 kV
Surge
EN 61000-4-5
Power port
± 2 kV line to earth, ± 1 kV line
to line
Signal ports
± 2 kV line to earth, ± 1 kV line
to line
RF conducted
EN 61000-4-6
Power port
10 V 80% AM (1 kHz), 0.15 – 80
MHz
Signal ports
10 V 80% AM (1 kHz), 0.15 – 80
MHz
Power frequency
magnetic field
EN 61000-4-8
Enclosure
300 A/m 0, 16.7, 50, 60 Hz
Pulsed magnetic
field
EN 61000-4-9
Enclosure
300 A/m
Radiated emission
EN 55022
Enclosure
Class A
FCC part 15
Enclosure
Class A
Conducted
emission
EN 55022
DC power ports
Telecommunication ports
Class B
Class B
FCC part 15
DC power ports
Class B
Содержание NE820
Страница 1: ...800xA Networks NE820 User Manual Power and productivity for a better worldTM ...
Страница 2: ......
Страница 3: ...800xA Networks NE820 User Manual ...
Страница 8: ...Licensing Information Safety 8 3BSE080635 ...
Страница 20: ...LED Indicators Power CPU Figure 8 LED Indicators Section 2 Interface specifications 20 3BSE080635 ...
Страница 37: ...Section 3 Interface Modules Safety Control Drawing 3BSE080635 37 ...
Страница 38: ...Section 3 Interface Modules 38 3BSE080635 ...
Страница 43: ......