24
3BSE080633
Pulsed
magnetic field
EN 61000-4-9
Enclosure
300 A/m
Radiated RF
immunity
EN 61000-4-3
Enclosure
10 V/m @ (80 – 800) MHz
20 V/m @ (800 – 1000) MHz
10 V/m @ (1400 – 2100) MHz
5 V/m @ (2100 – 2500) MHz
1 V/m @ (2500 – 2700) MHz
1 kHz sine, 80% AM
Conducted RF
immunity
EN 61000-4-6
Power port
10 V, 80% AM, 1 kHz; (0.15 – 80)
MHz
Signal ports
10 V, 80% AM, 1 kHz; (0.15 – 80)
MHz
Earth port
10 V, 80% AM, 1 kHz; (0.15 – 80)
MHz
Radiated RF
emission
EN 55022
Enclosure
Class A
FCC Part 15
Class A
Conducted RF
emission
EN 55022
Power port
Class B
Signal ports
Class B
Dielectric
strength
EN 60950-1
Power port to all
other ports
1.5 kVrms, 50 Hz, 1 min
Signal ports to
all other ports
1.5 kVrms, 50 Hz, 1 min
Environmental
Temperatures
Operating
–40 to +70°C (–40 to +158°F)*
Storage and
transport
–50 to +85°C (–58 to +185°F)
Humidity
Operating
5 to 95% relative humidity
Storage and
transport
5 to 95% relative humidity