Chapter 4 – Electrical Installation
4-6
Installation and Start-up Guide for NBRA-6xx
Cabling Procedure
•
At each end of both the ACS 600 cable and the resistor cable, twist
the screen wires together and connect them to the PE/chassis
terminal, along with conductor no. 3 (if present).
•
At both ends of the ACS 600 cable, connect conductor no. 1 to the
UDC+ terminal, and conductor no. 2 to the UDC– terminal.
•
At both ends of the resistor cable, connect conductor no. 1 to the R+
terminal, and conductor no. 2 to the R– terminal.
•
If clamping cable glands are used at cable entries, tighten them only
after making the terminal connections.