Power manual motor starter MS 325
According to IEC/EN 60 ... 947-1/-4-1/-5-1 for low-voltage switchgear,
Directive 94/9/EG for explosion-protected areas,
EN 60079-14 for electrical equipment for gas explosion endangered areas
EN 50281-1 for electrical equipment for dust explosion endangered area
E
Technical Data
Rated operating voltage U
e
[V]
690
Rated insulation voltage U
i
[V~]
690
Rated current
I
e
[A]
0.1 ... 25 / 14 ranges
Tripping class
10A
Rated frequency
[Hz]
50/60, other frequencies (16 2/3 … 400) on request
Electromagnetic tripping
Response values
0.1 ... 0.63 A: 7.5 - 12
times (x Ie)
0.63 … 2.50 A: 9
- 14
times
2.5 ...
6.30 A: 10
- 15
times
6.3 … 25
A: 12.5 - 17.5 times
Disconnected characteristics
according to
IEC/EN 60947-1
Service life
mechanical/electrically
100.000 connections
Permissible ambient temperature
- Storage
[°C]
-50 to +80
- Operation
[°C]
-20 to +50
Temperature compensation
[°C]
-20 to +50
Phase-failure protection
asymmetrical load activates premature release
Protection system
IP20
Connection cross sections
Clamp screw size: Pozidrive size 2
Torque of the cage clamps
max. 1.4 Nm
Wire
[mm²]
1 x 10 / 2 x 4
Rope, 7-stranded [mm²]
1 x 10 / 2 x 4
Wire strand
[mm²]
1 x 6
Mounting position
any
Mounting
can be snapped on 35 mm
Approvals and authorizations
see page 10