ABB MS132 Скачать руководство пользователя страница 5

  2CDC131022M6802f / 10.2016

5

MS132 / MS132-B

UL Information

For MS132 / MS132-B
Suitable for installation in an enclosure with minimum dimensions 
of 180 by 120 by 165 mm.

For bus bar PS1x and feeder S1-Mx

Device

Fuse/F1

SCC/F2

Voltage/
F3

S1-M-25+PS1-4-0+MS116/16

80 A

18 kA

480 V

S1-M3-x+PS1x+MS116/MS132

250 A

18 kA

480 V

S1-M3-x+PS1x+MS116/2,5/MS132/2,5

250 A

30 kA

480 V

S1-M3-x+PS1x+MS116/MS132/MS132-B

250 A

5 kA

600 V

Suitable for use in a circuit capable of delivering not more than F2 kA rms 
symmetrical amperes, F3 V maximum; when protected by F1 class fuse.

S1-M1-25

S1-M2-25

S1-M3-25

S1-M3-35

BS1-3

PS1- ... -65

x

x

x

1)

x

1)

x

PS1- ... -100

x

-

x

1)

x

1)

x

 

1)

 UL508 Type E 