![ABB MRP31.0 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/abb/mrp31-0/mrp31-0_manual_3410438015.webp)
Data at T
a
= 25 °C and rated values, unless otherwise indicated
—
General data
Supply voltage
24 V DC + 30% / - 20% (19.2 … 31.2 V DC)
Current consumption
30 mA
Supported Communication Protocols
Modbus RTU
Physical Interface
2-wire RS485
Integrated termination resistors
no
Possible bus addresses (set via UMC100)
1 ... 247
Supported baudrates
1200, 2400, 4800, 9600, 19200, 57600 Baud
Pollution degree
3
—
Standards / directives
Product standard
Modbus Specification
RoHS directive
2011/65/EU
—
Environmental data
Ambient air temperature
Operation 0 ... +60 °C
Storage
- 25 ... +70 °C
Vibration (sinusoidal) acc. to IEC/EN 60068-2-6
4 g / 10 .... 150 Hz (mounted on UMC100.3 / SMK3.0)
Shock (half-sine) acc. to IEC/EN 60068-2-27
15 g / 11 ms
—
General data
Degree of protection
IP20
Mounting
UMC100.3
SMK3.0
Mounting position
Any
Altitude
2000 - 4000 m at max. 40 °C
Duty time
100 %
Weight
0.039 kG
—
Technical data
15
U N I V ER S A L M OTO R CO N T R O L L ER U M C 10 0. 3 |
M R P31 .0 MODBUS TCP COM M U N I C ATI ON MODU LE M A N UA L