![ABB MicroSCADA Pro SYS 600C 2.93 Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/abb/microscada-pro-sys-600c-2-93/microscada-pro-sys-600c-2-93_product-manual_2386037.webp)
Table 6.3: IEEE Std 1613-2003 standard compliance
Severity level
Description
Type test
Level 4- ±4KV 5KHz All ports
EFT
IEEE C37.90.1
Level 4 -±8KV Contact/±15KV
Air
ESD
IEEE C37.90.3
Level 3-2.5KV common/Differ-
ential 1.25KV for Substation
Oscillatory Wave
IEEE C37.90.1
2000Vrms
Dielectric Strength
IEEE C37.90
5000V
Impulse Voltage
IEEE C37.90
-20%~+15%
DC Voltage Ranges
IEC 60870-2-1-1995
Level VR3- ≤5%
Voltage Ripple of DC
IEC 60870-2-1-1995
-40°C~+75°C
Nonoperational Temperature
Range
IEEE C37.90
-30°C (Start Up)~+65°C
Operational Temperature
Range
IEEE C37.90
Table 6.4: Environmental standard compliance
Severity level
Description
Type test
-30°C Start Up for 16 hours
Cold Temperature
IEC 60068-2-1
+65°C Start Up for 16 hours
Dry Heat Temperature
IEC 60068-2-2
Test Db 6 25°C/+55°C
93%/95% (1 cycle=24hrs)
Humidity (Damp heat, Cyclic)
IEC 60068-2-30
95% (non-condensing) 40°C 2d
Humidity (Damp heat, Steady
state)
IEC 60068-2-3
10-200-500-200-10Hz (1g/1.5g)
X/Y/Z axes
Vibration
IEC 60870-2-2-1996
10g 11ms X/Y/X axes
Shock
IEC 60870-2-2-1996
10g, repeat 1000 times X/Y/Z
axes
Bump (Packed)
IEC 60068-2-29-1987
10g, repeat 1000 times X/Y/Z
axes
Bump (Unpacked)
IEC 60068-2-29-1987
37
SYS 600C 2.93
MicroSCADA Pro
Product Guide
1MRS757729
16.11.2012
Issued:
A/16.11.2012
Version:
Содержание MicroSCADA Pro SYS 600C 2.93
Страница 1: ...MicroSCADA Pro SYS 600C 2 93 Product Guide ...
Страница 2: ...Trace back information Workspace Main version a11 Checked in 2012 11 13 ...
Страница 43: ......