64/86
MegaFlex 1000 to 1600
UPS User Manual / REV-A
7.2.2
Complete shut-down of the MegaFlex 1000 to 1600 as frequency converter
Note!
Follow this procedure only in case the UPS system and the Load must be completely powered-
down.
Initial status:
Load supplied by Inverter.
1. Perform the command
“
System shutdown”.
Perform the command “System shutdown” through
the screen:
Commands 1 / System shutdown /
SHUTDOWN
.
•
Load is disconnected from UPS.
•
Rectifier and Inverter are shut down and all contactors are
opened.
•
LED 1 (Rectifier) and LED 2 (Inverter) are OFF.
•
LED ALARM is lit.
2. Open the “Q1 – External UPS Output Circuit Breaker” (Pos. O).
3. Disconnect the Battery from the UPS by opening the “External Battery Breaker” (Pos. O).
Note!
Before performing the next procedure
(4) wait 5
minutes for DC-link Capacitors discharge.
Use the MEASURES/Rectifier screen to ensure that
the DC-link 1 and DC-link 2 voltage has reached
10Vdc.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
4. Disconnect the Utility from the input distribution.
End of Procedure
Danger!
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
Содержание MegaFlex 1000 UL S1
Страница 1: ... UPS USER MANUAL MegaFlex 1000 to 1600 kW UL S1 MegaFlex 1000 to 1600 kW UL S1 ...
Страница 85: ......