ABB MagMaster Скачать руководство пользователя страница 2

Flow Rng

Flow Unit

5.00000

m^3/Hr

PROGRAMMING

ANALOG OUTPUT

Display Setting

2
3
4
5
6
7
8
9

Seconds

2
3
4
8

15
30
60

120

Caution. Access is NOT possible without the

correct password. 'Lost' passwords can ONLY be
reset by the Service Engineer.

PARAMETER

DESCRIPTION

Alarm No1 Idle

Idle state for alarm output.
With no alarm active:

0 = Low (O/P transistor ON)
1 = High (O/P transistor OFF)

Alm No1 En

0 = Alarm output disabled (set to

idle state).

1 = Alarm output enabled.

Alm No1 Fault

Alarm occurs for System fault.

Alm No1 Fwd

Alarm occurs for forward flow.

Alm No1 Rev

Alarm occurs for reverse flow.

Alm No1 Cutoff

Alarm occurs for Pulse Output
Cutoff.

Alm No1 Mtsnsr

Alarm occurs for empty sensor.

Alm No1 Hi

Alarm occurs for Flow 

 ‘Alm Trip Hi’.

Alm No1 Lo

Alarm occurs for Flow 

 ‘Alm Trip Lo’.

Alm No1 Anlg

Alarm occurs for Analogue Output
over range.

Alm No1 Pls

Alarm occurs for Pulse Output over
range.

PARAMETER

DESCRIPTION

Tot Unit

Select totaliser measurement units.

Tot Mult

Select multiplier units required.

Tot ClrEn

Enter '1' to enable totaliser reset
function to be used from front panel.

PARAMETER

DESCRIPTION

Inpt

Set up external logic input function:
'Zero' sets flowrate output to zero.
'Hld' holds flowmeter output value.
'Clr' resets all totalizers.
'Anlg' selects Anlg No2 Range.

Inpt Idle

Enter inactive state of input contact:
'1' for Hi normal
'0' for Lo normal.

SECURITY PASSWORD

Login Key 1

Set Level 1 security password.

Login Key 2

Set Level 2 security password.

#  The maximum which can be entered must not exceed
21000. The value entered may be displayed with a small
error in the decimal digits e.g. 1.900 may be displayed as
1.899.  This is a display characteristic and the value 1.900
will be used by the MagMaster.

§ Select both parameters for bidirectional operation (e.g.
when dual current output is fitted). If both are zero, then I

OUT

is always 0%.

  On performing a Rapid Reset/Escape to return to
'Operation' level, 'Test Mode' is automatically cancelled.

Ø  If the sensor is empty or disconnected, the alarms
'MtSnsr' and 'Coil' will be displayed as appropriate.

PARAMETER CHANGES

FLOW MEASUREMENT

When a parameter is selected, which holds one or more
variable units e.g. 'Flow Unit' parameter which can be
Liters, Cubic meters, Gallons etc., proceed as follows to
change the units: ('Flow Rng' selected).

'Flow Unit' selected

Press 

 or 

 switch to change the units.

Note. The existing units will flash at the first

depression of the 

 or 

 switch, and further

switch depressions will change the type of units
displayed.

Depressing the 

 switch will now enter the newly

selected units.
This type of action is similar for all variable units.
Where numerical values are to be changed, initial
depression of the 

 or 

 switches cause the first of

five digits to be highlighted by a flashing cursor. Change
the value with the 

 and 

 switches, the particular

digit with the 

 switch, and enter the final selection with

the 

 switch.

The correct security level MUST be selected – see
SECURITY ACCESS.

Select the parameter to read the value, or to change it as
necessary.  All ‘live’ data displayed is updated each
second.

Use the 

 key to move between pages.

Use the 

 key to move between parameters.

The 

 and 

 keys change displayed values and units.

The 

 key will accept the chosen value or unit.

PARAMETER

DESCRIPTION

Flow Range

Enter main full scale (100%) flow
range (Upper Range Value) in
selected flow  units.   #

Flow Unit

Select Units as required.
Ltr (Liters)
m^3 (Cubic Meters)
IGal (Imp Gals)
UGal (U.S. Gals)
ft^3 (Cubic Feet)

Flow Mult

Select multiplier as required.
m (0.001)
c (0.01)
x1 (1)
h (100)
(1000)
M (1000000)

Flow Time

Select time units as required.
s (Second)
Min (Minute)
Hr (Hour)
Dy (Day)
Wk (Week)

Flow Resp

Nominal Time Constant for output.
Enter Display Setting from table
below for time constant required.

Flow %

Present flow as % of  range.

Flow Probe Ins

Probe Insertion Factor.

Flow Probe Prf

Probe Profile Factor

Flow Cutoff

Flow velocity in mm/sec. below
which flow set to 0.

PARAMETER

DESCRIPTION

Anlg Fsd

Enter output current in mA for 100%
flow (0 

 FSD 

 21)

Anlg Zero

Enter output current in mA for 0%
flow (0 

 ZERO 

 21)

Anlg No2

Full scale flow range for 2nd analog
range, as % of main flow range.

Anlg mA

Present output current (mA)

Anlg Dir Fwd

Output responds to forward
flow if set to '1'. §

Anlg Dir Rev

Output responds to reverse
flow if set to '1'. §

OUTPUT PULSE

PARAMETER

DESCRIPTION

Pls Fact

Enter required output pulses per
flow volume unit.#

Pls Cutoff

Flow rate (%) below which pulse
output and totaliser cease to operate.

Pls Max

Maximum output frequency in Hz.

Pls Hz

Display of present output frequency in
Hz (live value).

Pls Idle

Idle state for Pulse Output with no
output pulse (e.g. at zero flow).

0 = Low (output transistor  ON)
1 = High (output transistor OFF)

Pls Size

Enter output pulse width in msecs.
(Value will be rounded up to nearest
10ms). Set to ‘0’ for square wave
output.

ALARMS (CONTD.)

PARAMETER

DESCRIPTION

Alarm No2 Idle

Identical to, but independent of
Alarm No1 above.

Alarm No2 Pls

Alarm occurs for Pulse Output
over range.

TEST MODE

PARAMETER

DESCRIPTION

Disp Res

Enter number of decimal places
required on flow display (0 to 5).

Disp Mode

Serial Communication display
mode (Read Only) – attempts to
edit this parameter result in display
of 'Keypad Version No.' with
eventual return to normal
operation.

DISPLAY RESOLUTION

PARAMETER

DESCRIPTION

Test Mode

Set to '1' to enable.

Test Flow

Displays present flowrate.
If in 'Test Mode', any value may be
entered manually. ‡

Test %

Flowrate as a percentage

Test Hz

Output Frequency

Test mA

Output Current

Test Vel

Flow Velocity in sensor

Test Alm

Shows present active alarms
sequentially. ('Clr' indicates no
alarms are active).   Ø

Test Txv

Live flow velocity (uncorrected for
sensor calibration).

SENSOR CALIBRATION

PARAMETER

DESCRIPTION

Snsr No

Serial No. (Up to 13 characters)

Snsr Tag

Tag No. (If required).

Snsr Size

Sensor calibrated bore (mm).

Snsr Vel

Display of present velocity.

Snsr Fact 1

Snsr Fact 2

Sensor calibration data –

Snsr Fact 3

should agree with sensor data label

Snsr Fact 4

PARAMETER

DESCRIPTION

Mtsnsr Trip

Set empty pipe detector trip
threshold.

Mtsnsr mV

Measured value related to fluid
conductivity.

ALARMS

EMPTY PIPE DETECTION

PARAMETER

DESCRIPTION

Alarm trip Hi

High flow alarm trip point as % of
range.

Alarm Trip Lo

Low flow alarm trip point as % of
range.

Alm Trip Hyst

Enter hysteresis for alarms as % of
range.

Alm Trip Disp

Set to ‘1’ if Hi/Lo Alarms are to be
displayed.

INPUT CONTACT

TOTALIZER

Отзывы: