M4M FIRMWARE UPDATE

 

 

 

4

/

10 

C.

 

Follow the instructions in case M4M is a slave device in master/slave 

RS485 network or M4M is directly connected via serial port to PC:

 

TIP

: In order to directly connect M4M to PC, a RS-485/USB con-

verter is needed. 

 

Verify that Modbus RTU communication settings of M4M are equal to 

Modbus RTU settings of the master device. 

 

If the master device is an ABB cloud access point, default settings are re-

ported below:

 

• Baud Rate = 19200

 

• Protocol = 8E1 (8 bit data, even parity and 1 bit stop)

 

• RTU address for Master Device = 1

 

• RTU address for M4M slave device: to be inserted starting from 2 to 247.

 

TIP

: Each device shall be provided with a different slave address. 

Otherwise, only one of the devices with the same slave address 

can be recognized.

 

2.2

 

M4M Ethernet 

 

(M4M 20 Ethernet, M4M 30 Ethernet)

 

A.

 

Steps to set Modbus TCP/IP communication parameters are described in 

section "Communication" of M4M 20 and M4M 30 user manual.

 

To reach the settings section, on the device, go to "HOME" 

 "Configura-

tion" 

 "Communication" 

 "Modbus TCP/IP". Parameters that can be set 

are DHCP, IP address, Subnet mask, Gateway and TCP port.

 

In the "DHCP" section, select between Enable and Disable.

 

In the "IP address" section, select the desired address of the device or 

read the current IP address if the DHCP support is enabled.

 

TIP

: In case of ABB cloud access point, DHCP on M4M should be 

disabled (as default) and its TCP port, which is already enabled, 

should be at the default value (502).

 

TIP

: In case of ABB cloud access point, IP of M4M shall be in the 

range of the sub-network where the cloud access point is con-

nected, which must be provided with access to the internet.

 

B.

 

According to the architecture, follow the instructions

 

1.

 

M4M directly connected to laptop via Ethernet port

 

Laptop shall be connected to same Ethernet network where the 

M4M is connected. To access IP settings in Windows, access laptop 

“Control Panel” 

 ”Network and Sharing Center” 

 ”Change 

adapter settings” 

 right click on “Local Area Connection (LAN)” 

 ”Properties”>”Internet Protocol Version” and “Properties”.

 

2.

 

M4M connected in the local area network 

 

Laptop shall be connected to the same local area network as M4M.

 

 

Содержание M4M

Страница 1: ...2CSG445053D0201 V 1 00 1 10 COMMISSIONING GUIDELINE M4M Firmware update Getting started ...

Страница 2: ...ial and tools needed 3 2 Initial settings on M4M device 3 2 1 M4M Modbus RTU M4M 20 Modbus M4M 20 I O M4M 20 Rogowski M4M 30 Modbus M4M 30 I O M4M 30 Rogowski 3 2 2 M4M Ethernet M4M 20 Ethernet M4M 30 Ethernet 4 3 FW update procedure via EPiC desktop 5 ...

Страница 3: ...hernet for both M4M 20 and M4M 30 ver sions 2 1 M4M Modbus RTU M4M 20 Modbus M4M 20 I O M4M 20 Rogowski M4M 30 Modbus M4M 30 I O M4M 30 Rogowski A Check that Modbus RTU cable connected to the ABB power meter is cor rectly connected in particular make sure that W1 A W2 B TIP in case the device is not communicating re cable the device by switching terminals hence W1 B W2 A B Steps to set Modbus RTU ...

Страница 4: ...device go to HOME Configura tion Communication Modbus TCP IP Parameters that can be set are DHCP IP address Subnet mask Gateway and TCP port In the DHCP section select between Enable and Disable In the IP address section select the desired address of the device or read the current IP address if the DHCP support is enabled TIP In case of ABB cloud access point DHCP on M4M should be disabled as defa...

Страница 5: ...vice in the RS 485 architecture e g PLC the master should be disabled in order to use EPiC desktop and perform the FW update B Open EPiC desktop in the Scan tab C Configure the scanning via communication protocol 1 Via Modbus RTU M4M Modbus Click on Configure under Serial port Select port name baudrate parity slave addresses of all devices connected via Modbus RTU to be updated Press OK ...

Страница 6: ...on Configure under Ethernet In the section IP addresses insert the IP address of M4M Ether net in the list of IP addresses to be scanned It is possible to either add IP addresses one by one Use IP address list or input IP ad dress range Use IP address range Press Ok ...

Страница 7: ... on Scan E EPiC desktop allows to visualize the product related pages including dashboard and Modbus map reading via Classic View In the Information section of the Dashboard it is possible to check what is the firmware version currently installed on M4M F Click on Tools ...

Страница 8: ...irmware update option in order to upload the FW version previously downloaded from the ABB Library here Please extract the enc file from the downloaded zip I Please click on the Select file from Computer option and select the enc related to the latest FW version of M4M ...

Страница 9: ...th the M4M during the FW update process in or der to have a successful update K A loading bar will inform regarding the status of the FW update After reaching the 100 M4M will start the rebooting process for few minutes while checking the new firmware The screen will turn black and the red LED lights will be on Please do not unplug the M4M s auxiliary power sup ply during this operation ...

Страница 10: ...M4M FIRMWARE UPDATE 10 10 L As the FW update is completed successfully a banner will appear on Ekip Connect to inform the user ...

Отзывы: