LevelMaster 7100 User manual 2105835 Rev AA |
52
Figure 46: Activating the LevelMaster application
17. Remain on the main PCCU32 screen.
18. Proceed to section 6.2,
Set up general and communications
, next.
Set up general and communications parameters
The following information will detail the steps to set up the number of tanks and assign the communications port for the
LevelMaster.
IMPORTANT NOTE:
For XFCs or XRCs, ensure that the serial communication port has the correct
communication module (RS-485). For RMC-100s, ensure that the hot-swappable module is inserted and set for
RS-485 operation.
To set up the number of tanks and communications parameters:
1. Expand
the
Communications
node in the navigation tree.
2. Expand
the
LevelMaster
node in the navigation tree.
3. Click
Setup
under LevelMaster.
4. On
tab, the value of the Device/APP ID may be changed. Any name change will be reflected in the tree-view.
5.
Type the number of tanks that will handled by the application. Figure 47 displays an application handling 2 tanks.
6. Click
Send
.