![background image](http://html.mh-extra.com/html/abb/knox/knox_original-instructions-manual_1212008.webp)
2TLC172250M0201, rev. D
8
www.abb.com/jokabsafety
2013-08-12
Electrical connections
– Knox 2X
Locking
The locking signal at pin-5 must be continuously applied (+24 VDC) to keep the device locked. When the locking
signal is applied, it may take up to 2 seconds for Knox to fully reach the locked state.
Unlocking
Knox will be unlocked when no locking signal is applied. It may take up to 2 seconds until Knox is unlocked.
NB: Knox 2X will retain locked/unlocked state if the device power supply (pin-1 and -3) is cut off.
Warning
! The system must be connected using a fuse of max 6A.
ADAM
EDEN
Knox 2X
4
1
3
2
Motor
5
M12 5-pole male seen
from cable side
M12 5-pole female
seen from cable side
5-pole M12-connector:
1) Brown:
+24 VDC
2) White:
Dynamic input signal
3) Blue:
0 VDC
4) Black:
Dynamic output signal
5) Grey:
Lock (+24 VDC)
Unlock (0 VDC)
Caution!
All cable colours according to ABB Jokab Safety standard cable.
Содержание Knox
Страница 12: ...2TLC172250M0201 rev D 12 www abb com jokabsafety 2013 08 12 Assembly conventional door ...
Страница 13: ...2TLC172250M0201 rev D 13 www abb com jokabsafety 2013 08 12 ...
Страница 16: ...2TLC172250M0201 rev D 16 www abb com jokabsafety 2013 08 12 Assembly sliding door ...
Страница 17: ...2TLC172250M0201 rev D 17 www abb com jokabsafety 2013 08 12 ...