QUICK START GUIDE

 

Page 10

 

© 2021 ABB. All rights reserved.

 

 

 

Precautions

 

• 

Install,  service,  and  operate  equipment  only  by  professional,  skilled  and  qualified  personnel  who  have  the  necessary 
knowledge  and  practical  experience  with  electrical  equipment  and  who  understand  the  hazards  that  can  arise  when 
working on this type of equipment.

 

• 

Disconnect  batteries  from  outputs  and/or  follow  safety  procedures  while  working  on  equipment.  Batteries  may  be 
connected in parallel with the output of the rectifiers. Turning off the rectifiers will not necessarily remove power from 
the bus.

 

• 

Do not disconnect permanent bonding connections unless all power inputs are disconnected.

 

• 

Verify  that  equipment  is  properly  safety  earth  grounded  before  connecting  power.  High  leakage  currents  may  be 
possible.

 

• 

Exercise care and follow all safety warnings and practices when servicing this equipment. Hazardous energy and voltages 
are  present  in  the  unit  and  on  the  interface  cables  that  can  shock  or  cause  serious  injury.  When  equipped  with  ringer 
modules, hazardous voltages will be present on the ringer output connectors.

 

• 

Use the following precautions in addition to proper job training and safety procedures:

 

• 

Use only properly insulated tools.

 

• 

Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).

 

• 

Follow Lock Out Tag Out (LOTO) procedures: customer specified, site specific, or general as appropriate. Disconnect 
all  power input before servicing the equipment. Check for multiple power inputs.

 

• 

Wear safety glasses.

 

• 

Follow Personal Protective Equipment requirements: customer specified, site specific, or general as appropriate.

 

• 

Test circuits before touching.

 

• 

Be aware of potential hazards before servicing equipment.

 

• 

Identify exposed hazardous electrical potentials on connectors, wiring, etc.

 

• 

Avoid contacting circuits when removing or replacing covers;.

 

• 

Use a personal ESD strap when accessing or removing electronic components.

 

• 

Personnel  with  electronic  medical  devices  need  to  be  aware  that  proximity  to  DC  power  and  distribution  systems, 
including batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic devices, 
such as pacemakers. Effects decrease with distance.

 

Содержание J2013001

Страница 1: ...for details and accessories Tools required Step 1 Mount Shelf 1 Reposition mounting ears as required 4 screws each Torque to 25 in lb 2 8Nm Phillips screwdriver 2 Position the Initial Panel immediately above the rectifier shelf with Controller Position Supplementary Panels immediately above another Panel 3 Install Inter Shelf brackets between adjacent shelves optional Torque to 25 in lb 2 8Nm Phil...

Страница 2: ...RETURN bus landings of the top or bottom Shelf 850036871 lug adapter is supplied with primary distribution shelves Lug landing 1 4 holes on 5 8 centers hardware provided lug not provided Torque all hardware to 65 in lb 7 3 Nm 7 16 socket Step 4 Connect Shelf DC Connections are on the rear under covers Bus Connection to an adjacent shelf Install inter shelf buses joining 48V and RETURN bus connecti...

Страница 3: ...troller if present cable provided 2 Connect alarm cables between all Distribution Shelves RETURN bus Connections covers shown 48V bus Connections covers removed 2 Adjacent shelves Dual Lug Landings stand alone Shelf Inter shelf bus Alarm Cable Primary Distribution Shelf to Primary Rectifier Shelf Primary Rectifier Shelf with Controller Primary Distribution Shelf Alarm Cable Shelf to Shelf Suppleme...

Страница 4: ...t Connections only Verify that breaker is OFF or not installed 1 Remove Cover 2 Connect cables with suitable lugs to 48Vdc BATT and POS RTN landings 3 Torque to 65 in lb 7 3 Nm 7 16 socket 4 Replace cover Step 7 Connect Bullet Circuit Breaker Loads skip if not present Load connections are labeled 48Vdc LOAD and POS RTN Load Breakers have Black handles CAUTION Verify that breaker is OFF or not inst...

Страница 5: ... 9 Connect GMT Style Fuse Loads skip if not present skip if not present Connections for Load GMT Fuses to GMT terminal blocks identified as 48VDC and RTNS on labels above each row of terminals blocks Wire Size 24 12AWG Strip Length 0 35 9mm 1 Verify that fuse is not installed 2 Strip wires 3 Insert wires into terminal blocks labeled 48VDC and associated RTNS 4 Tighten screw 4 in lb 0 45 Nm 5 Pull ...

Страница 6: ...positions as specified in Site Engineering Instructions Bullet Breakers CAUTION 1 Install breakers oriented as shown Orientation is different for Left and Right breakers 2 Install proper breaker type in Battery and Load positions Battery Breakers Yellow handle in Battery Position Right positions only Load Breakers Black handle in Load Positions Right and Left positions 1 Remove Retention Cover 2 s...

Страница 7: ...each Breaker is OFF 3 Insert each Breaker fully into its position oriented with ON position at top 4 Remove cover knockouts for installed positions 5 Replace Cover 2 thumb screws 6 Turn each Breaker ON GMT Style Fuses 1 Insert each GMT style fuse fully into its position oriented as shown Load Breaker Positions Battery or Load Breaker Positions Breaker Guard Orientation Right Positions Breaker Guar...

Страница 8: ...it as necessary Verify Disconnect Contactor Settings if disconnect contactor is present A Controller Display Follow the menu path Menu Configuration Contactor Interfaces Built In type LVBD or LVLD and Menu Configuration Disconnects LVBD or LVBD 1 3 edit as necessary B Web Pages or EasyView2 Select the Settings Tab Contactors DCNC1 type LVBD Select Edit button edit settings as necessary Reference D...

Страница 9: ... ordering guide Size as required by the National Electric Code NEC and or local codes Safety Tested Limits Refer to the equipment ratings to assure current does not exceed Continuous Load List 1 60 of protector rating Maximum Load List 2 typically end of discharge 80 of protector rating GMT Style Fuses Use only fuses provided with safety caps Field wired Conductors Follow all National Electric Cod...

Страница 10: ... equipped with ringer modules hazardous voltages will be present on the ringer output connectors Use the following precautions in addition to proper job training and safety procedures Use only properly insulated tools Remove all metallic objects key chains glasses rings watches or other jewelry Follow Lock Out Tag Out LOTO procedures customer specified site specific or general as appropriate Disco...

Страница 11: ...QUICK START GUIDE Page 11 2021 ABB All rights reserved Notes ...

Страница 12: ...ccept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2021 ABB All rights reserved ABB 601...

Отзывы: