EKIP COM MODBUS TCP MODULE
Ekip Com Modbus TCP is an accessory module that can function as a communication module integrating the
ITS2.1 in an industrial remote supervision and control network.
As Communication module, it can be connected to an Ethernet network with the Modbus TCP communication,
and allows:
Connect the ITS to the network, with dialog functionality
Provide the status information of the switch or fusegear (open, closed)
Information
Since the module allows access to the data contained in the ITS, it can only be connected
to networks that meet all the necessary requirements for safety and prevention of
unauthorized access (for example, the network of the control system of an installation).
It is the installer’s responsibility to ensure that all the necessary safety measures are
adopted (for example, firewalls, and so on). The module cannot be connected directly to
the Internet, it is recommended to connect it only to dedicated Ethernet networks, with
the Modbus TCP communication protocol.
For the communication bus, a cable of type Cat.6S/FTP must be used (Cat.6 with S/FTP double shielding).
The following table illustrates the possible signals of Ekip com Modbus TCP module, and their meaning:
LED
Indication
Description
Power LED, green
Off
Power supply absent
On fixed
Power supply and communication with the device
present
On, with two quick flashes per
second
Power supply present, and communication with device
absent
Link LED, green
Off
Connection error (signal absent)
On, fixed
Correct connection
Activity LED, yellow
Off
No activity on the line
On, flashing
Activity present on the line (in reception and/or
transmission)
For the installation of the Ekip Com Modbus TCP module, please refer to Slimeline/InlineII/Standalone ITS
installation instruction.
Link