background image

 

QUICK START GUIDE

 

Page 5

 

© 2021 ABB. All rights reserved.

 

 

 

IEC Style AC Cords

 

12 AWG

 

Part Num

 

CC848847368

 

No plug

 

8 ft

 

CC848850792

 

5

-

15P

 

8 ft

 

CC848850801

 

5

-

20P

 

8 ft

 

CC848850826

 

6

-

15P

 

8 ft

 

CC848850834

 

6

-

20P

 

8 ft

 

850044361

 

L5

-

15P

 

15 ft

 

850044362

 

L5

-

20P

 

15 ft

 

CC848895961

 

L6

-

20P

 

15 ft

 

Information: Alarm Connections

 

See the Infinity S

-

Flex Power System Brochure for details. 

 

Alarm connections are on the rear of the shelf.

 

Change alarm descriptions via LAN port (Web pages) or Craft port (EasyView2) when required.

 

  Pin

 

Color

 

Signal

1

 

 Default

2

 

 

 

User Configurable Alarm Input

 

 

 

White

 

User Configurable Alarm Input

 

Aux Major

 

 

 

 

Alarm Battery Supply (ABS)

 

 

 

Power Major Relay Return

 

PMJ Return

 

 

 

Power Minor Relay Return

 

 

 

Red/White

 

Relay 1 Return

 

 

 

White/Black

 

 

 

 

 

 

 

 

   

 

 

Red

 

User Configurable Alarm Input

 

SPD Fail

 

 

Green

 

User Configurable Alarm Input

 

 

 

 

 

 

 

 

Power Major Relay

 

 

 

 

Power Minor Relay

 

PMN

 

 

Green/White

 

 

BD/VLV

 

 

White/Red

 

Relay 2 Return

 

 

 

 

 

Fuse Alarm Major (FAJ)

 

1.

 

Relays 1 

-

 4 are user configurable.

 

2.

 

Customer specific factory defaults 

-

 see the Quick Start Guide Supplement.

 

3.

 

Positive Temperature Coefficient resistor protected battery voltage provides up to 0.5A for external alarm circuits.

 

Information: Rectifier and Converter Options

 

Содержание Infinity S J5964803 L209

Страница 1: ... 65 in lb 0 10Nm Step 1 Mount Shelf 1 Reposition mounting ears as required 4 screws each Torque to 25 in lb 2 8Nm Phillips screwdriver 2 Install Inter Shelf brackets between adjacent shelves optional Torque to 25 in lb 2 8Nm Philli screwdriver 3 Attach shelf to the frame using a minimum of four screws two on each side 12 24 provided Torque to 35 in lb 4Nm 5 16 socket Universal Power Shelves accept...

Страница 2: ... Install inter shelf buses joining 24V 48V and RETURN outputs of adjacent shelves Torque to 65 in lb 7 3 Nm Cable Connection to stand alone shelf Lug Landings 2 x 1 4 on 5 8 center 0 7 18mm max tongue width Connect cables with suitable lugs to 24V 48V and RETURN Torque to 65 in lb 7 3 Nm Step 3 Connect AC Input External Feed Protector see Information Rectifier Options Danger Turn OFF and lock out ...

Страница 3: ...same number Step 8 Install Signal and Communications Cables Connectors are on rear figure above 1 J1 Alarms office alarms and signals See Information Alarm Connections 2 J3 4 Shelf to Shelf communication Connect adjacent shelves Connect 1 Wire Battery Temp and Voltage Monitor optional 3 J5 LAN Connect to Ethernet network 4 J7 Distribution Panel signals Connect to Distribution Panel if present Step...

Страница 4: ... 44A 20A 20A Converter Input DC Output DC Voltage Current3 Voltage Current NE030DC48A 81A max 75A NE040DC48A 108A max 50A 24V Orange NE075DC24A 54A max 100A Open the faceplate by sliding the faceplate latch to the left until the faceplate releases and swings outward Slide the unit into the slot until it engages with the back of the shelf Swing the faceplate closed to fully seat the unit Verify the...

Страница 5: ...urn Power Minor Relay Return Red White Relay 1 Return White Black Red User Configurable Alarm Input SPD Fail Green User Configurable Alarm Input Power Major Relay Power Minor Relay PMN Green White BD VLV White Red Relay 2 Return Fuse Alarm Major FAJ 1 Relays 1 4 are user configurable 2 Customer specific factory defaults see the Quick Start Guide Supplement 3 Positive Temperature Coefficient resist...

Страница 6: ... ports 1 are suitable for connection to intra building or unexposed wiring or cabling 2 can be connected to shielded intra building cabling grounded at both ends Grounding Bonding Network Isolated Ground Plane Isolated Bonding Network or Integrated Ground Plane Mesh Bonding Network or Common Bonding Network Installation Environment Network Telecommunication Facilities OSP or where NEC applies DC R...

Страница 7: ...ibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2021 ABB All rights reserved ABB 601 Shiloh Rd Plano ...

Отзывы: