QUICK START GUIDE

 

Page 1

 

© 2021 ABB. All rights reserved.

 

 

 

Infinity S 19" Universal Power Shelf

 

Models: J5964803 L209

-

L216 

 

• 

Sockets 

-

 

5/16”, 7/16”, 

etc.

 

• 

Screwdrivers 

-

 Philips #1 and #2, Flat small 

 

Inter

-

Shelf Bracket

 

Step 2 

-

 Connect Chassis Ground

 

Lug  Landings:  #10  double

-

hole  on  5/8

-

inch  center 

(lugs not provided)

 

Some  applications  may  rely  on  frame  mounting 

screws for shelf ground omitting the chassis ground 

cable.

 

Minimum 10 AWG wire is recommended.

 

Torque  10

-

32  screws  to  30  in

-

lb  (3.4Nm) 

-

 

5/16” 

socket.

 

Knockout

 

2 Adjacent Shelves

 

Mounting Ears

 

Chassis Ground

 

AC Wiring Box

 

Tools required

 

• 

Wire cutters and strippers

   

• 

Cable crimpers

 

 

• 

Torque wrench 

-

 0

-

65 in

-

lb (0

-

10Nm)

 

Step 1 

-

 Mount Shelf

 

1.

 

Reposition  mounting  ears  as  required 

-

  4  screws  

each.  Torque  to  25  in

-

lb  (2.8Nm) 

-

  Phillips 

screwdriver.

 

2.

 

Install Inter

-

Shelf brackets between adjacent 

shelves (optional). Torque to 25 in

-

lb (2.8Nm) 

-

 Philli 

screwdriver 

 

3.

 

Attach shelf to the frame using a minimum of four 

screws (two on each side) 

-

 12

-

24 (provided). Torque 

to 35 in

-

lb (4Nm) 

-

 

5/16” 

socket.

 

Universal Power Shelves 24V and –

48

V rectifiers and converters.

 

Primary shelf (L209, L211, L213, & L215) includes controller slot. Install shelf immediately below distribution, if used. 

Expansion shelf (L210, L212, L214, & L216) includes cables and hardware to connect to an adjacent shelf.

 

No vertical spacing is required. Provide 2 inch minimum clearance at back of shelf for rectifier airflow.

 

Refer to Infinity S Flex Power System Brochure for details and accessories.

 

Содержание Infinity S J5964803 L209

Страница 1: ... 65 in lb 0 10Nm Step 1 Mount Shelf 1 Reposition mounting ears as required 4 screws each Torque to 25 in lb 2 8Nm Phillips screwdriver 2 Install Inter Shelf brackets between adjacent shelves optional Torque to 25 in lb 2 8Nm Philli screwdriver 3 Attach shelf to the frame using a minimum of four screws two on each side 12 24 provided Torque to 35 in lb 4Nm 5 16 socket Universal Power Shelves accept...

Страница 2: ... Install inter shelf buses joining 24V 48V and RETURN outputs of adjacent shelves Torque to 65 in lb 7 3 Nm Cable Connection to stand alone shelf Lug Landings 2 x 1 4 on 5 8 center 0 7 18mm max tongue width Connect cables with suitable lugs to 24V 48V and RETURN Torque to 65 in lb 7 3 Nm Step 3 Connect AC Input External Feed Protector see Information Rectifier Options Danger Turn OFF and lock out ...

Страница 3: ...same number Step 8 Install Signal and Communications Cables Connectors are on rear figure above 1 J1 Alarms office alarms and signals See Information Alarm Connections 2 J3 4 Shelf to Shelf communication Connect adjacent shelves Connect 1 Wire Battery Temp and Voltage Monitor optional 3 J5 LAN Connect to Ethernet network 4 J7 Distribution Panel signals Connect to Distribution Panel if present Step...

Страница 4: ... 44A 20A 20A Converter Input DC Output DC Voltage Current3 Voltage Current NE030DC48A 81A max 75A NE040DC48A 108A max 50A 24V Orange NE075DC24A 54A max 100A Open the faceplate by sliding the faceplate latch to the left until the faceplate releases and swings outward Slide the unit into the slot until it engages with the back of the shelf Swing the faceplate closed to fully seat the unit Verify the...

Страница 5: ...urn Power Minor Relay Return Red White Relay 1 Return White Black Red User Configurable Alarm Input SPD Fail Green User Configurable Alarm Input Power Major Relay Power Minor Relay PMN Green White BD VLV White Red Relay 2 Return Fuse Alarm Major FAJ 1 Relays 1 4 are user configurable 2 Customer specific factory defaults see the Quick Start Guide Supplement 3 Positive Temperature Coefficient resist...

Страница 6: ... ports 1 are suitable for connection to intra building or unexposed wiring or cabling 2 can be connected to shielded intra building cabling grounded at both ends Grounding Bonding Network Isolated Ground Plane Isolated Bonding Network or Integrated Ground Plane Mesh Bonding Network or Common Bonding Network Installation Environment Network Telecommunication Facilities OSP or where NEC applies DC R...

Страница 7: ...ibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2021 ABB All rights reserved ABB 601 Shiloh Rd Plano ...

Отзывы: