ABB i-bus® KNX
PARAMETERS
CAUTION
To ensure that the device functions properly, a reset must be performed each time the assignment of
the outputs is changed.
Note
The possible options and the standard option depend on the selection made in the following parame-
ters:
•
•
Activate basic-stage heating via
•
Activate basic-stage cooling via
Option
Internal channel output (valve)
The control value is output on the internal channel output. In addition, the control value is output via
one of the following group objects:
•
Status Control value additional-stage heating
•
Status Control value additional-stage heating
Group object
The control value is output via one of the following group objects:
•
Status Control value additional-stage heating
•
Status Control value additional-stage heating
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
all options except
Deactivated
• The parameter is in the parameter window
.
7.4.10
Activate additional-stage cooling via
This parameter is used to define whether the control value for activating additional-stage cooling is out-
put via an internal output or a group object.
CAUTION
To ensure that the device functions properly, a reset must be performed each time the assignment of
the outputs is changed.
Note
The possible options and the standard option depend on the selection made in the following parame-
ters:
•
Activate basic-stage heating via
•
Activate basic-stage cooling via
•
Activate additional-stage heating via
Option
Internal channel output (valve)
The control value is output on the internal channel output. In addition, the control value is output via
one of the following group objects:
•
Status Control value additional-stage cooling
(DPT 1.001)
•
Status Control value additional-stage cooling
(DPT 5.001)
Group object
The control value is output via one of the following group objects:
•
Status Control value additional-stage cooling
(DPT 1.001)
•
Status Control value additional-stage cooling
(DPT 5.001)
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage cooling [controller]
all options except
Deactivated
– Parameter
all options except
Deactivated
• The parameter is in the parameter window
.
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B