ABB i-bus® KNX
GROUP OBJECTS
Function
Group object name
Data point
type
Length
Flags
Error "Fill level alarm" receipt
Channel X – General
DPT 1.005
1 bit
C R
T
The group object sends the error status for the cyclical monitoring of the group object Fill level alarm [input x] on the bus (ABB i-bus® KNX).
The monitoring cycle is set in the parameter
Time interval for cyclical monitoring
.
Telegram value:
•
1 = Error
•
0 = No error
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage cooling [controller]
\
all options except
Deactivated
–
Option
Via group object
•
–
Option
Activated
–
Monitor receipt of group object "Fill level alarm"
\
Option
Activated
Error "Operating mode" receipt
Channel X – General
DPT 1.005
1 bit
C R
T
The group object sends the error status for the cyclical monitoring of the group object
Operating mode normal (master)
on the bus (ABB i-bus® KNX).
The monitoring cycle is set in the parameter
Time interval for cyclical monitoring
.
Telegram value:
•
1 = Error
•
0 = No error
Prerequisites for visibility
•
\ Option
Controller channel
•
–
Option
Activated
–
Monitor receipt of group object "Operating mode normal (master)"
\
Option
Activated
Status byte channel
Channel X - General
Non DPT
1 byte
C R
T
This group object sends the following status information on the bus (ABB i-bus® KNX):
•
Bit 7: Unused
•
Bit 6: Unused
•
)
–
1 = Active
–
0 = Inactive
•
Bit 4: Manual operation
–
1 = Active
–
0 = Inactive
•
Bit 3: Manual valve override
–
1 = Active
–
0 = Inactive
•
Bit 2: Forced operation
–
1 = Active
–
0 = Inactive
•
Bit 1: Building Protection (→
Explanation of the operating modes, Page 174
)
This bit is always 0 for an actuator channel (Device function).
–
1 = Active
–
0 = Inactive
•
Bit 0: Operating mode override
This bit is always 0 for an actuator channel (Device function).
–
1 = Active
–
0 = Inactive
Note
The device is in safety mode after starting, because the controller has not yet received a valid temperature value.
Prerequisites for visibility
•
This group object is always visible.
Error "Control value" receipt
Channel X – General
DPT 1.005
1 bit
C R
T
The group object sends the error status for the cyclical monitoring of the following group objects on the bus (ABB i-bus® KNX):
•
•
The monitoring cycle is set in the parameter
Time interval for cyclical monitoring
.
Telegram value:
•
1 = Error
•
0 = No error
Prerequisites for visibility
•
\ Option
Actuator channel
•
–
Option
Activated
–
Monitor receipt of "Control value heating/cooling" group objects
Option
Activated
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
153