PARAMETERS
7.4.100
Heat protection setpoint (building protection, cooling)
This parameter is used to define the setpoint temperature that must not be exceeded in the
Building
Protection cooling operating mode.
More information: →
Explanation of the operating modes, Page 174
Note
The temperature value specified here must be higher than the value in the parameter
.
If the device is in the
Cooling operating mode, the setpoint is active in the following cases:
• Controller receives the status "Window open", "Fill level alarm" or "Dew point alarm"
• The controller is deactivated via group object
• Controller is placed in the
Building Protection
operating mode via group objects
Operating mode override (master)
Option
27 … 35 … 45 °C
Prerequisites for visibility
\ Option
Controller channel
• The parameter is in the parameter window
7.4.101
Economy cooling setpoint
This parameter is used to define the setpoint temperature for the
Economy cooling operating mode.
More information: →
Explanation of the operating modes, Page 174
Note
The temperature value specified here must be higher than the value in the parameter
. A difference of at least 2 K is recommended.
Note
The controller ensures that the setpoint temperature is not fallen below when the actual temperature
decreases. The operating mode is not changed.
Option
10 … 29 … 40 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Option
Comfort, Standby, Economy, Building Protection
– Parameter
Setpoint specification and adjustment
Option
Absolute
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
114