Description of application and parameters
Application "1-button short-long operation"
KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905
│33
10.6.2 General parameters - Reaction at brief operation
Options:
No reaction
Value 1
Value 2
Alternating value1/value2
Here it is specified whether the "Value 1" or the "Value 2" is sent out for a short operation of the
button.
Alternatively, Value1/Value2 can also be alternatingly set for a short operation, i.e. after Value 1
was sent (or received), a renewed operation will send out a Value 2. After it is operated again,
Value 1 is again sent out.
The "No reaction" setting causes no telegram to be sent out for a short operation of the button.
10.6.3 General parameters - Reaction at long operation
Options:
No reaction
Value 1
Value 2
Alternating value1/value2
Here it is specified whether the "Value 1" or "Value 2" is sent out for a long operation of the
button.
Alternatively, Value1/Value2 can also be alternating set for a long operation, i.e. after Value 1
was sent (or received), a renewed operation will send out a Value 2. After it is operated again,
Value 1 is again sent out.
The "No reaction" setting causes no telegram to be sent out for a long operation of the button.
10.6.4 Extended parameters - Time for long operation
Options:
00.300 ... 03.000
A differentiation can be made between a short or long operation of the button. With a short
operation of the button, the next level forward is switched to in each case. With a long
operation, the first level is activated. Thus with a long button press a jump back from every
position to the first level is possible, without having to run through the remaining levels.
Via the "Duration of long operation", the time is specified from which a long button press is
recognised and the object values are reset. The first level must be set again with a press of the
button. Any time from 0.3 to 3 seconds can be set. A typical value after which a jump-back to
level 1 is made is 0.4 s.