Commissioning
© 2006 ABB STOTZ-KONTAKT GmbH
13
ABB i-bus
®
EIB / KNX
Maximum telegram rate
Options:
1/2/3/5/10/20 telegrams/second
To control the bus load, it is possible to limit the
Maximum telegram rate
per second with this parameter.
Example: With the setting
5 telegrams/second
a maximum of 5 telegrams
will be sent in a second.
Switch positions with new start recall after [1...255 seconds]
Options:
1…20…255 seconds
With this parameter the time interval is set at which the switch positions can
be recalled on the monitored channels after a new start.
Example: If the Data Logging Unit is restarted and the setting is set to
2
seconds
, after 2 seconds it will commence to recall all the switch
positions of the parameterised channels.
Switch positions cyclic recall every [0...255 minutes, 0 = deactivated]
Options: 0…1…255 minutes
0 = function deactivated
With this parameter the time interval is set after which the switch positions
are recalled on a cyclic basis.
Note:
The set cycle time applies for all channels. The function can be
enabled or inhibited for each channel.
If the switch positions are recalled cyclically, ensure that on the
recalling device, e.g. a switch actuator channel, the R flag is set
in the communication object to be recalled. Otherwise the Data
Logging Unit can not recall the switch position.
Break between two recall telegrams [1...255 seconds]
Options:
1…2…255 seconds
In order to allow co-ordinated recall of the individual switch positions a pause
is set between two recall telegrams.
Note:
If a switch actuator does not respond, the telegram will be
repeated twice.