15
5.7.4 General specifications of fixed circuit-breakers
with rh lateral operating mechanisms for ABB UniAir switchgear (12 - 17.5 - 24 kV)
Circuit-breaker
HD4/UniAir 12
HD4/UniAir 17
HD4/UniAir 24
Standards
IEC 62271-100
•
•
•
CEI EN 62271-100
(dossier 7642)
•
•
•
Rated voltage
Ur [kV]
12
17.5
24
Rated insulation voltage
Us [kV]
12
17.5
24
Withstand voltage at 50 Hz
Ud (1 min) [kV]
28
38
50
Impulse withstand voltage
Up [kV]
75
95
125
Rated frequency
fr [Hz]
50-60
50-60
50-60
Rated thermal current (40°C)
Ir [A]
630
800
1250
630
800
1250
630
800
1250
Rated duty breaking capacity
(symmetrical rated short-circuit current)
Isc [kA] 12.5
–
–
12.5
–
–
12.5
–
–
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
25
25
25
–
–
–
–
–
–
Short-time withstand current (3 s)
Ik [kA] 12.5
–
–
12.5
–
–
12.5
–
–
16
16
16
16
16
16
16
16
16
20
(8)
20
20
20
(8)
20
20
20
20
20
25
25
25
–
–
–
–
–
–
Making capacity
Ip [kA] 31.5
–
–
31.5
–
–
31.5
–
–
40
40
40
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
63
63
63
–
–
–
–
–
–
Sequence of operations
[O - 0.3s - CO - 15s - CO]
•
•
•
Opening time
[ms]
45
45
45
Arcing time
[ms]
10...15
10...15
10...15
Total break-time
[ms]
55…60
55…60
55…60
Closing time
[ms]
80
80
80
Overall dimensions
(maximum)
H [mm] 748
(4)
- 735
(5) (6)
- 704.5
(7)
748
(4)
- 735
(5) (6)
- 704.5
(7)
748
(4)
- 735
(5) (6)
- 704.5
(7)
L [mm] 374
(4)
- 464
(5) (6)
- 286.5
(7)
374
(4)
- 464
(5) (6)
- 286.5
(7)
374
(4)
- 464
(5) (6)
- 286.5
(7)
D [mm]
1189
1189
1189
Pole center-distance [mm]
300
300
300
Weight
(1)
[kg] 108
(4) (6)
- 110
(5)
- 103
(7)
108
(4) (6)
- 110
(5)
- 103
(7)
108
(4) (6)
- 110
(5)
- 103
(7)
Absolute gas pressure (nominal duty value)
[kPa]
380
380
380
Application of PR521 protection device
In [A] 40 - 80 - 250 - 1250
(2)
40 - 80 - 250 - 1250
(2)
40 - 80 - 250 - 1250
(2)
Application of REF 601 protection device
•
(3)
•
(3)
•
(3)
Standardized dimensions table
TN 7235
(4)
1VCD000102
(4)
1VCD000102
(4)
TN 7274
(5)
1VCD000103
(5)
1VCD000103
(5)
TN 7273
(6)
1VCD000104
(6)
1VCD000104
(6)
TN 7275
(7)
1VCD000104
(6)
1VCD000104
(6)
Wiring diagram
without relay / with PR521 1VCD400018
(4) (5) (6)
1VCD400018
(4) (5) (6)
1VCD400018
(4) (5) (6)
1VCD400017
(7)
1VCD400017
(7)
1VCD400017
(7)
with REF 601 1VCD400116
(4) (5) (6)
1VCD400116
(4) (5) (6)
1VCD400116
(4) (5) (6)
1VCD400114
(7)
1VCD400114
(7)
1VCD400114
(7)
Operating temperature
[°C]
- 5 ... + 40
- 5 ... + 40
- 5 ... + 40
Tropicalization
IEC: 60068-2-30, 60721-2-1
•
•
•
Electromagnetic compatibility
IEC 62271-1
•
•
•
1)
increase the indicated weight by 20 kg for circuit-breakers with PR521 / REF 601 devices and 3 current sensors (15 kg only with 2 current sensors)
(2)
rated current of the current sensors (the PR521 device and the current sensors are available on request)
(3)
the REF 601 device and the current sensors are available on request. The rated current of the REF 601 must be set in the relay and must be compatible with the rated current of the
circuit-breaker. The rated current that can be set with CEI 0-16 is 80 A or 250 A. With the CEI 0-16 version of REF 601, the circuit-breaker is always supplied with 3 phase sensors
(Rogowsky coils) on the circuit-breaker itself, one 40/1 A closed-core toroidal TA and a -MU undervoltage release for relay-controlled opening
(4)
HD4/UniAir for Unit P1/F (unit with plug-in circuit-breaker)
(5)
HD4/UniAir-2R for Unit P1E/2R (unit with plug-in circuit-breaker on the supply and load sides)
(6)
HD4/UniAir-A for Unit P1/A (unit with fixed “upside-down” circuit-breaker)
(7)
HD4/UniAir-F for P1/F Unit (unit with fixed circuit-breaker without wheels and cabled to terminal box); the 12-17.5-24 kV types available are 630 A, 12.5 and 16 kA only
(8)
at 12 and 17.5 kV and at 630 A rated current, the rated short-time withstand current is 20 kA for 1 second
H
L
D
Содержание HD4/R
Страница 2: ......
Страница 21: ...21 7 9 Overall dimensions 7 9 1 Fixed HD4 R 12 24 kV 630 1250 A TN 7237 Figure 9 ...
Страница 22: ...22 7 9 2 Fixed HD4 R 12 24 kV 630 1250 A TN 7234 Figure 10 ...
Страница 23: ...23 Type A A B C 630 307 5 35 8 800 1250 302 5 40 10 7 9 3 Fixed HD4 R 36 kV 630 1250 A TN 7238 Figure 11 ...
Страница 24: ...24 7 9 4 Plug in HD4 S 12 24 kV 630 1250 A TN 7236 Figure 12 ...
Страница 25: ...25 7 9 5 HD4 Uniair 12 24 kV 630 1250 A TN 7235 Figure 13 ...
Страница 26: ...26 7 9 6 HD4 Uniair F 12 24 kV 630 A TN 7275 Figure 14 ...
Страница 27: ...27 7 9 7 HD4 Uniair 2R 12 24 kV 630 1250 A TN 7274 Figure 15 ...
Страница 28: ...28 7 9 8 HD4 Uniair A 12 24 kV 630 1250 A TN 7273 Figure 16 ...
Страница 29: ...29 7 9 9 HD4 UniMix F 12 24 kV 630 1250 A TN 7366 Figure 17 ...
Страница 30: ...30 7 9 10 HD4 R SEC 12 24 kV 630 800 A 1VCD003536 Figure 18 ...
Страница 37: ......