Recommendations for positioning
The maximum stresses in the oil at the surface of the shield
insulation and the parts surrounding the bushing must be
limited to those values normal for insulated conductors and
other similar components in the same transformer.
The withstand voltage in a specific case depend upon many
factors beyond control of the bushing manufacturer.
Therefore the configuration and distances given below are
only intended as guidelines.
ABB can provide assistance with field calculations to
confirm the compatibility between the transformer and the
bushing.
Table 8.
Type
GSA-OO
Internal
insulation level
of transformer
kV
Shield
Distance to
earthed parts
(with
shield) R1
mm
(without
shield) R2
mm
73
350-140
LF 170 020-S
130
90
LF 170 020-T
123
550-230
LF 170 020-S
200
145
LF 170 020-T
145
650-275
LF 170 020-S
228
165
LF 170 020-T
170
750-325
LF 170 020-S
260
190
245
1050-460
LF 170 046-AT
400
270
R1
Min. R5
Distance to
uninsulated
detail
60°
Space for current
transformer
Distance to flat surface e.g.
tank or core clamp
R2
Min. R2
45°
—
09 Recommendations for positioning.