The Shunt Trip or Shunt Trip with Lockout is installed in the 
accessory  compartment  through  the  front  of  the  circuit 
breaker in the position shown in Figure 2. 

Shunt Trip or 

Shunt Trip with Lockout 

Bell Alarm  Bell Alarm-

with 

Alarm Only

Lockout 

Undervoltage Release 

shunt  trip  occurs,  with  the  procedure  described  in 
the Accessory Configuration section.
Mount the supplied step-down transformer near the 
circuit breaker.
Connect  the  control wiring  for  either Shunt  Trip  to 
the primary side of the transformer, marked as the H 
numbered  terminals.  Table  3  lists  the  correct 
transformer primary taps.

Connect  the  secondary  side  of  the  transformer, 
marked as the X numbered terminals, to terminals 31 
and 32 of  the terminal block on the right side of the 
breaker.  Table  3  lists  the  correct  transformer 
secondary taps. 

Primary 

Secondary 

Catalog

 

Number/ 

Control

 

Voltage 

Connections 

Connections 

9T58K0042 

H1

H4(1) 

X1,

 

X2 

480 

V

 

9T58K0062

H1, H4 

X1,

 

X3 

600 

V

 

Test  the  Shunt  Trip  to  ensure  proper  operation, 
according to the procedures below.
Reconnect power to the circuit breaker and  any other 
accessories.
Close  and  lock  or  seal  the  door  over  the  accessory 
compartment  and  Trip  Unit  to  prevent  unauthorized 
changes  to  Trip  Unit  settings  and  to  keep 
contaminants out of empty accessory slots. 

Accessory Configuration 

This  section  only  applies  if  Alarm-Alarm  Bell  Only  or  Bell 
Alarm with Lockout accessories are installed in the breaker, 
along with a MicroVersaTrip Plus or MicroVersaTrip PM Trip 
Unit. If the breaker is equipped with a Power+ Trip Unit, the 
factory  default  settings,  listed  in  Table  4,  can  not  be 
changed. 
The Shunt Trip accessory can be configured to activate the 
Bell Alarm-Alarm Only or Bell Alarm with Lockout accessories 
if a shunt trip occurs. The configuration can be changed by 
removing  the  Trip  Unit  from  the  breaker,  setting  the  DIP 
switches on the rear of the Trip Unit, and reinstalling the Trip 
Unit. Figure 4 illustrates the Trip Unit rear DIP switches and 
their  functions. Table  4  lists  the  switch  functions and  the 
factory settings for each. 

Use the following procedure to install the Shunt Trip accessory 

into the Shunt Trip slot of the accessory compartment: 

Tighten the locking screw on the front of the accessory 
until it is snug(9 in-lb). 

(1) A jumper must be placed from  H2 to H3. 

Open the hinged door over the accessory compartment 
and Trip Unit.
To remove an existing accessory, loosen the accessory 
locking screw and pull the accessory out with the Rating 
Plug Removal Tool (catalog number TRTOOL).
Insert the Shunt Trip accessory into the proper slot, as 
illustrated in Figure 3. The Shunt Trip accessory is keyed 
for the correct slot in the accessory compartment. If the 
accessory cannot be fully seated in the compartment, 
check that the compartment position is correct. 

WARNING: 

480Vac and 600 Vac Shunt Trip accessories must 

be used with the supplied step-down transformer. 

AVERTISSEMENT:

 

Les  modules  de  d

é

clenchement  shunt 

480  Vac  et  600  Vac  doivent 

ê

tre  utilis

é

s  avec  le 

transformateur abaisseur de tension qui est fourni. 


Figure 2 Accessory compartment on front of circuit breaker, with Shunt Trip slot indicated. 

1.

2.

3.


Figure 3. Inserting a Shunt Trip into the accessory compartment. 

4

.

CAUTION: 

Over tightening the locking screw may damage 

or distort the case of the accessory.

ATTENTION: 

Le serrage excessif de  la vis de

 verrouillage

 

peut d

é

former le bo

î

tier d'accessoire. 


Table 3. Primary and secondary connections for step-down transformers. 

9

.

10

.

11

.

If the breaker is equipped with a MicroVersaTrip Plus or 
MicroVersaTrip PM Trip Unit, the Shunt Trip accessory 
can be configured to activate installed Bell Alarm-Alarm

 

Only or Bell Alarm with Lockout accessories when a

 

5

.

8

.

9

.

7

.

6

.

2

Содержание GE SPST480

Страница 1: ...Trip and Shunt Trip with Lockout Installation The Shunt Trip and Shunt Trip with Lockout accessories shown in Figure1 can be installed in 800 4000 ampere frame Power Break II circuit breakers These accessories allow the breaker to be tripped electrically from a remote location In addition to providinga trip signal to the breaker the Shunt Trip accessories can be set up to interact with other Power...

Страница 2: ...urs The configuration can be changed by removing the Trip Unit from the breaker setting the DIP switcheson the rear of the Trip Unit and reinstallingthe Trip Unit Figure 4 illustrates the Trip Unit rear DIP switches and their functions Table 4 lists the switch functions and the factory settings for each Use the followingprocedure to installthe Shunt Trip accessory into the Shunt Trip slot of the a...

Страница 3: ...dure 1 Turn off the power to the Shunt Trip 2 Close the breaker contacts 3 Apply at least 55 of the rated ac voltage to the Shunt Trip the breaker should trip immediately 4 If a Bell Alarm Alarm Only or Bell Alarm with Lockout is present ensure that they activate or do not activate as selected by the MicroVersaTrip Plus or MicroVersa Trip PM Trip Unit DIP switches Figure 4 Accessory switch on the ...

Страница 4: ...ip Unit would be powered up by an energized Shunt Trip accessory Verify that the breaker is closed Check that the Shunt Trip with Lockout control power is applied at greater than 55 of the rated ac voltage Check that the accessory is completelyinserted re insert if necessary Note that an otherwise underpowered Trip Unit is powered by an energized Shunt Trip accessory Check that the Shunt Trip with...

Отзывы: