332 Verification and validation
8. Deactivate SS1 function.
9. Acknowledge the function.
Repeat this procedure for all redundant input(s), and with all safety functions that use
the inputs.
Validation of safety I/O’s
The safety I/O configuration (SAFEIO.xx parameters) and functionality including the
test pulsing must be verified according to the application requirements. If safety relay
outputs and their feedbacks are used in the application, the related diagnostic
functions must also be verified.
Validation of the general settings
Make sure that the general settings of the safety functions are configured correctly
according to your design. For a configuration example, see section
. Check the values of these parameters:
•
•
•
•
•
•
•
•
.