224 Configuration
Configuring general settings
How to configure general settings
To configure the general settings, set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter group
FSOGEN
on
page
180
.
Example:
The figure below shows an example I/O set-up:
• After power-up the acknowledgement can only be performed manually
FSOGEN.41 Power-up acknowledgement =
Manual
).
• Acknowledgement button is connected to input X114:4
=
DI X114:4
).
•
50.00 Hz
. Use the same value with the
drive parameter
99.08. Motor nominal frequency
, and the value on the motor type
designation label.
•
=
1360.0 rpm
. Use the same value with the
drive parameter
99.09 Motor nominal speed
, and the value on the motor type
designation label.
•
90.0 rpm
. Use a suitable (low
enough) value. The motor must coast to stand still in a relatively short time.
• External requests ending in the drive STO are reported to the drive as events
FSOGEN.61 STO indication ext request
=
Event
).
• Safety function limit hits are reported as faults
=
Fault
).
• No output connected for the completion of stop functions (STO, SSE, SS1)
None
).
= DI X114:4
= 50.00 Hz
= 1360.0 rpm
= Manual
= Event
= Fault
Drive
event
system
= 90.0 rpm
M
= None
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...