258 Configuration
Configuring SLS
To configure the SLSn (n = 1…4), set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter groups
on
page
on page
For more information on the SLS function, see page
.
Depending on the application, set the negative and positive SLS and SLS trip limits
separately.
How to configure SLSn with time monitoring
Example:
The figure below shows an example of the SLS1 function with time
monitoring set-up:
• SLS1 function activated (
=
Version 1
)
• time monitored deceleration ramp
SLS activation monitoring method
Time
)
• deceleration ramp according to drive parameters (always with time monitoring)
• SLS activation delay: 2000 ms (
2000 ms
)
• automatic acknowledgement (
=
Automatic
)
• redundant SLS activation button connected to input
=
DI X113:2 & X114:2
)
• single output connected (
DO X114:7
)
• positive limits: SLS 1200.0 rpm, trip limit 1320.0 rpm
=
1200 rpm,
=
1320 rpm
).
• negative limits: SLS -900.0 rpm, trip limit -1020.0 rpm
=
-900 rpm,
-1020 rpm
).
• See also section
.
Note
: The difference between the SLS limit and the corresponding SLS trip limit must
be at least 0.1 rpm.
Note
: If you also use the SMS function, the SLS trip limits positive and negative must
be below the speed defined by parameter
and above the speed
defined by parameter
, respectively.
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...