248 Configuration
Configuring SSE
To configure the SSE function, set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter groups
page
on page
.
For more information on the SSE function, see page
Note:
Always set the parameters related to the SSE function to have the correct trip
limit hit and fault reaction behavior. For example, the FSO module activates the SSE
function if an I/O failure occurs.
How to configure SSE with immediate STO
Example:
The figure below shows an example of the SSE function with immediate
STO set-up:
• drive STO is activated immediately after the SSE request
Immediate STO
)
• automatic acknowledgement (
=
Automatic
)
• redundant emergency stop button connected to input
=
DI X113:1 & X114:1
)
• no outputs connected
• delay for restarting the drive: 1500 ms. This is the estimated time in which the
motor coasts to a stop from the maximum speed.
(
Time to zero speed with STO and modoff
1500 ms
)
• no brake (
=
None
).
= Immediate STO
= 1500 ms
SSE activated
Time
Speed
Inputs
Outputs
= Automatic
= None
= DI X113:1 & X114:1
= None
= None
= None
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...