Configuration 227
How to configure a cascaded system
This example shows how to configure the SSE function in a cascaded system
(Cascade A) as shown in section
on page
.
1. Define one of the FSO modules as the master and the other FSO modules are
followers:
•
In the master FSO:
=
A = master, B = master.
•
In the follower FSOs:
=
A = follower, B = follower.
2. Connect a digital input to the corresponding digital output in the cascaded system
(single cascade X113:2 -> X113:8):
•
=
X113:2 -> X113:8.
3. Set the acknowledgement method in the master FSO modules (
Manual
):
•
Manual
4. Set the acknowledgement method in the follower FSO modules (
Automatic
).
•
Automatic
5. Set the digital inputs and outputs of the SSE function as defined for the cascaded
system:
•
The SSE function is activated from a redundant digital input in the master FSO
(
=
DI X113:1&X114:1
)
•
The SSE function is cascaded with a single connection in the follower FSOs
(
DI X113:2
,
=
DO X113:8
).
Note
: Do not use the completed output of the safety function as the cascaded
output (parameter (
None
).
6. Set the digital input for the acknowledgement button in the master FSO module:
•
DI X113:4.
7. Set the other parameters related to the SSE function as defined in section
on page
.
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...