Ex relevant specifications for operation in Div. 1
SM/FEX300/FEX500/FM/CSA-EN
FEX300, FEX500
EN - 27
Table 3: Fluid temperature (Ex data) for ProcessMaster models FEP325, FEP525
Nomi
nal di
ame
ter
Desig
n
Tem
p
erat
ure
class
Ambient temperature
(- 40 °C)
1)
- 20 °C ... + 40 °C
(- 40 °C)
1)
- 20 °C ... + 50 °C
(- 40 °C)
1)
- 20 °C ... + 60 °C
Not thermally
insulated
Thermally
insulated
Not thermally
insulated
Thermally
insulated
Not thermally
insulated
Thermally
insulated
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
DN 3 ... D
N
100
NT
T1
130 °C
110 °C
110 °C
110 °C
110 °C
HT
180 °C
160 °C
150 °C
160 °C
150 °C
NT
T2
130 °C
110 °C
110 °C
110 °C
110 °C
HT
180 °C
160 °C
150 °C
160 °C
150 °C
NT
T3
130 °C
110 °C
110 °C
110 °C
110 °C
HT
180 °C
160 °C
150 °C
160 °C
150 °C
NT
T4
120 °C
110 °C
110 °C
110 °C
110 °C
HT
120 °C
120 °C
120 °C
120 °C
120 °C
NT
T5
85 °C
85 °C
85 °C
85 °C
85 °C
HT
85 °C
85 °C
85 °C
85 °C
85 °C
NT
T6
70 °C
70 °C
70 °C
70 °C
70 °C
HT
70 °C
70 °C
70 °C
70 °C
70 °C
DN 125 ...
DN 20
00
NT
T1
130 °C
110 °C
110 °C
110 °C
110 °C
HT
180 °C
160 °C
150 °C
160 °C
150 °C
NT
T2
130 °C
110 °C
110 °C
110 °C
110 °C
HT
180 °C
160 °C
150 °C
160 °C
150 °C
NT
T3
130 °C
110 °C
110 °C
110 °C
110 °C
HT
180 °C
160 °C
150 °C
160 °C
150 °C
NT
T4
125 °C
110 °C
110 °C
110 °C
110 °C
HT
125 °C
125 °C
125 °C
125 °C
125 °C
NT
T5
90 °C
90 °C
90 °C
90 °C
90 °C
HT
90 °C
90 °C
90 °C
90 °C
90 °C
NT
T6
75 °C
75 °C
75 °C
75 °C
75 °C
HT
75 °C
75 °C
75 °C
75 °C
75 °C
1)
Low-temperature version (option)
NT: standard sensor design, T
medium
maximum 130 °C (266 °F).
HT: high-temperature sensor design, T
medium
maximum 180 °C (356 °F).
Not thermally insulated: The flowmeter sensor is not surrounded by pipe insulation material.
Thermally insulated: The flowmeter sensor is surrounded by pipe insulation material.
Note
The standard version includes explosion protection for gases and dust.
• If the installation location for the device is classified as a potentially explosive area for gases and dust, the temperature data
in the "Gas & dust" columns in the table must be taken into consideration.
• If the installation location for the device is classified as a potentially explosive area for gases only, the temperature data in
the "Gas" columns in the table must be taken into consideration.