![ABB FENA-01 Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/abb/fena-01/fena-01_quick-installation-and-start-up-manual_3320148002.webp)
2
Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters. See
the appropriate drive firmware manual.
Basic parameter settings
Protocol-specific parameter settings
To take the settings into use, validate and refresh the parameters with parameter
51.27 FBA par refresh
.
Connectivity configuration
To access the configuration web page:
1. Open a web browser and type the IP address of the adapter module in the address field.
2. Log in with a user name (
admin
) and a password (The last six digits of the MAC address of the adapter
module, in upper case letters, without hyphens. Eg, if MAC ID is 00-1C-01-00-2F-73, the password is
002F73
).
Further information
Index
Name
Value
20.01
Ext1 commands
Fieldbus A
22.11
Speed ref1 source
FBA A ref 1
28.11
Frequency ref1 source
FBA A ref 1
50.01
FBA A enable
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
50.02
FBA A comm loss func
Fault
PROFINET IO
Ethernet/IP
Index
Name
Value
Index
Name
Value
51.02
Protocol/Profile
PNIO ABB Pro
51.02
Protocol/Profile
EIP AC/DC
51.04
IP configuration
Static IP
51.04
IP configuration
Set the IP address
according your network
configuration.
51.05...08
IP address
0.0.0.0
51.05...08
IP address
51.09
Subnet CIDR
0
51.09
Subnet CIDR
52.01
FBA A data in1
SW 16bit
51.23
Speed scale
128
52.02
FBA A data in2
Act 16bit
53.01
FBA A data out1
CW 16bit
Modbus/TCP
53.02
FBA A data out2
Ref1 16bit
Index
Name
Value
51.02
Protocol/Profile
Modbus/TCP
51.04
IP configuration
Set the IP address
according your network
configuration.
51.05...08
IP address
51.09
Subnet CIDR
See the latest version of
FENA-01/-
11/-21 Ethernet adapter module user's
manual
(3AUA0000093568 [English])
in ABB library
For more information on ABB fieldbus
options and protocols, see the field-
bus communications web page
new.abb.com/drives/connectivity/field-
bus-connectivity
3A
X
D
500005
51
31
6
Re
v A (
E
N
) 2
0
19
-1
1-
22
© Copyright 2019 ABB. All rights reserved.
Specifications subject to change without notice.
abb.com/drives