Start-up

When the module is connected to the drive, the drive control program sets the applicable parameters. 
See the appropriate drive manual.

Basic parameter settings

To take the settings into use, validate and refresh the parameters with parameter 

51.27 FBA par refresh

.

Further information

Index

Name

Value

20.01

Ext1 commands

Fieldbus A

22.11

Speed ref1 source

FBA A ref 1

28.11

Frequency ref1 source FBA A ref 1

50.01

FBA A enable

Enable (or select the option slot in which the module is installed)

50.02

FBA A comm loss func Fault

51.02

Node ID

Set the node address of the device.

51.03

Bi

t

 rate

Set the bit rate for the CANopen interface.

51.05

Profile

The ABB Drives communication profile is the default value.

See the latest version of 

FCAN-01 CANopen adapter 

module user's manual

 (3AFE68615500 [English]) in ABB 

library (

www.abb.com/drives/documents

)

.

For more information on fieldbus options and protocols 
provided by ABB Drives, see the fieldbus 
communications web page 
(

new.abb.com/drives/connectivity/fieldbus-connectivity

).

Pin allocation for [X1]

Bus termination

Bus termination is required to prevent signal reflections 

from the bus cable ends. The module is not equipped with 
internal bus termination. Therefore, the first and last 
nodes of the bus must be included with bus termination. 

In the this diagram, the built-on terminations of the D-SUB 
connectors at the first and last nodes are switched on.

According to CANopen specification CiA 301

.

Pin

 Description

1

Not in use

2

CAN_L 

CAN_L bus line 

3

CAN_GND

CAN ground

4

Not in use

5

CAN_SHLD

Optional CAN shield

6

GND

Optional ground

7

CAN_H

CAN_H bus line 

8

Not in use

9

CAN_V+

Not supported.

5

9

6

1

SUB-D9 
(male)

CANopen

ON

CANopen

CANopen

CANopen

.

OFF

.

OFF

ON

 

3AXD50000158195 Rev A (EN) 2017-11-23

FCAN-01 manual