F-400 Fire rated switch-disconnectors

Wiring

Interruptor-seccionador para

altas temperaturas

Fire rated switch disconnector

IMP-40/6T

 

Class F300

EN12101-3 

IEC947-3

AB55641F3

 6P

 20A

Retighten all connection 

screws during installation

25...40A 2Nm

63...125A 3,5Nm

!

PZ2

PZ3

Interruptor-seccionador para

altas temperaturas

Fire rated switch disconnector

IMP-40/6T

 

Class F300

EN12101-3 

IEC947-3

AB55641F3

 6P

 20A

2

1

Interruptor-seccionador para

altas temperaturas

Fire rated switch disconnector

IMP-40/6T

 

Class F300

EN12101-3 

IEC947-3

AB55641F3

 6P

 20A

Ph2

x4

3

4

Supply

Outgoing

Attention: 

IP65 cable

glands has 

to be used

Enclosure and cover 

earthing

25...63A     1,6Nm

section 2,5...16mm

2

!

PZ2

PZ3

100...125A    3,5Nm

section 6...50mm

5

When using EMC cable glands/ cables 

make sure cable shield is properly 

grounded in cable gland.

Содержание F-400

Страница 1: ... INSTALL ATION INSTRUCTION F 400 Fire rated switch disconnectors OKA 25 125_F4_ F 400 Fire rated switch sisconnectors OKA 25 125 _F4_ ...

Страница 2: ... Table of contents 2 03 Diagrams 04 Wiring 04 Connection 05 Fixing 05 Padlockable handle 06 Dimensions 08 Warning sheet ...

Страница 3: ... 4P 2 1 4 3 6 5 8 7 0 1 1 2 3 4 5 6 7 8 T1 T2 T3 T4 N L3 L4 N L2 L1 Switch disconnector 6P 2 1 4 3 6 5 8 7 10 9 12 11 0 1 L3 L1 L2 L3 L2 L1 1 2 3 4 5 6 7 8 9 10 11 12 T1 T2 T3 T1 T2 T3 Auxiliary contacts are 25A Auxiliary contacts identification number change based on the number of switch cells Early break 2 1 4 3 6 5 8 7 10 9 12 11 0 1 ...

Страница 4: ...25 40A 2Nm 63 125A 3 5Nm PZ2 PZ3 In te rr u p to r se cc io n ad o r p ar a al ta s te m p er at u ra s F ire ra te d sw itc h di sc on ne ct or IM P 4 0 6T C la ss F 30 0 E N 12 10 1 3 IE C 94 7 3 A B 55641F 3 6P 20A 2 1 Ph2 x4 3 4 Supply Outgoing Attention IP65 cable glands has to be used Enclosure and cover earthing 25 63A 1 6Nm section 2 5 16mm2 PZ2 PZ3 100 125A 3 5Nm section 6 50mm 5 When usi...

Страница 5: ...63A 100A 125A connect screws M5 M5 M8 M8 M8 torque Nm 2 0 2 0 3 5 3 5 3 5 terminal flexible wire section mm2 2 5 16 2 5 16 6 50 6 50 6 50 Fixing Switch Type A B C Ø x nº OKA 25_F4_ 116 96 5 5 x 4 OKA 40_F4_ 146 126 5 5 x 4 OKA 63 125_F4_ 230 206 6 5 x 4 A B C Padlockable handle x4 ø 8 màx ...

Страница 6: ...e OKA 25_F4_ F 400 25A Box size OKA 40_F4_ F 400 40A 64 160 90 124 74 130 90 124 M25 64 74 160 90 124 M32 64 74 AB55241F4 EN12101 3 IEC947 3 3P 40A Class F 400 160 90 124 M32 64 74 3 4P 1xM25 6P 2xM25 3 4P 1xM25 6P 2xM25 3 4P 1xM32 6P 2xM32 3 4P 1xM32 6P 2xM32 ...

Страница 7: ...0 6P 2xM40 3 4P 1xM40 6P 2xM40 Switches F 400 6P Aux C not contemplated 3 4 Poles 6 Poles 25A Top 1xM25 2xM25 Botton 1xM25 2xM25 40A Top 1xM32 2xM32 Botton 1xM32 2xM32 63A Top 1xM40 2xM40 Botton 1xM40 2xM40 100 125A Top 1xM40 2xM40 Botton 1xM40 2xM40 M40 M40 111 145 64 64 74 148 250 63A 100 125A ...

Страница 8: ...s ABB Oy P O Box 622 FI 65101 Vaasa Finland abb com lowvoltage Copyright 2020 ABB All rights reserved Specifications subject to change without notice 34 OKA25 125_F4 rev B 1SCC 340174M0201 29 11 2019 6302502 6 4359 ...

Отзывы: